TERMINAL DESCRIPTIONS

HEATING COOLING VERSION

Terminal changes when using SH(X) humidifier version are indicated.
Terminal
Type
H N
Power Supply
GND
Ground
LmA B
Modbus
ECO
AO
ECM Motor Output
PWM
ECM Motor Feedback
ECM
ECM Common
MHW
AO
Modulating heating
MCW
AO
Modulating cooling
MEc
AO
Modulating economizer
MSp
AO
VFD command speed
MPP
Profile pressure
AO
AL
DO
Alarm
SA
DO
Supply air
DM
DO
Damper actuator enable
Common to output set
CMa
COM
'a'
Common to output set
CMb
COM
'b'
STG1
DO
Cooling stage #1
STG2
DO
Cooling stage #2
STG3
DO
Cooling stage #3
STG4
DO
Cooling stage #4
STG5
DO
Cooling stage #5
HiS
DO
High Speed
Exl
Exhaust fan low
DO
Common to output set
CMc
COM
'c'
MBV
AO
Modulating ball valve
Modulating combustion
MCA
AO
air
FbG
AI
Feedback Gas
IOM74
Name
Connect to chassis.
Internal network.
ECM motor output controls signal.
ECM motor speed feedback signal.
ECM output signal common.
Hot water coil valve actuator. 0V=off.
Chilled water coil valve actuator. 0V=off.
Economizer / Mixbox actuator. 0V=closed.
VFD control signal.
Modulating profile pressure damper actuator
output.
Alarm contact for annunciation.
Blower enable contact.
Two position actuator control.
Common power relays 'a', above.
Common power relays 'b', below.
Output stage #1 cooling, powered from
common 'b'.
Output stage #2 cooling, powered from
common 'b'.
Output stage #3 cooling, powered from
common 'b'.
Output stage #4 cooling, powered from
common 'b'.
Output stage #5 cooling, powered from
common 'b'.
High speed fan start contact.
Single or low speed exhaust fan start
contact.
Common power relays 'c', below.
Modulating gas valve actuator output.
Modulating combustion air actuator output.
Compares the ball valve actuator feedback
signal to the demand signal.
10
A
Description
Value
24 Vac
0-10 Vdc
PWM
0-10 Vdc
0-10 Vdc
0-10 Vdc
0-10 Vdc
0-10 Vdc
0-10 Vdc
24 Vac
24 Vac
24 Vac
24/120 Vac
24/120 Vac
24/120 Vac
24/120 Vac
24/120 Vac
24/120 Vac
24/120 Vac
24/120 Vac
24/120 Vac
24/120 Vac
0-10 Vdc
0-10 Vdc
0-10 Vdc