US English translation of the German original operating manual This operating manual is part of the technical documentation. It provides technicians and system managers with the necessary information on: • Installation • Installation and commissioning • Operation • Maintenance www.schubert-system-elektronik.de...
Page 2
To be observed in general To be observed in general Safety instructions This document contains instructions that you must follow for your personal safety and to prevent damage to property. The instructions are marked by a warning triangle and are graded according to the degree of risk. Symbol with signal word: DANGER Imminent danger to life and health of persons.
Page 3
Products from Schubert System Elektronik GmbH comply with the relevant harmonized European standards (EN) for the respective area of application. Warranty The agreements stipulated in the General Terms and Conditions of Business (GTC) apply to Schubert System Elektronik GmbH equipment. Safety instructions The safety instructions specified in this document must be observed during the commissioning and ongoing operation of the products.
Page 4
To be observed in general EU Declaration of Conformity The product from Schubert System Elektronik GmbH complies with the directives listed in the “Technische Daten” chapter. The requirements are assessed on the basis of the standards referenced therein. The EU Declaration of Conformity and the associated documentation are provided in accordance with the directives at:...
Table of contents Table of contents Characteristic ............................... 1 Overview ................................. 1 Block diagram ................................ 2 Installation ................................3 Unpacking and checking delivery contents ......................3 Storage and transport ............................3 Installation ................................3 Temperature ................................3 Ventilation ................................4 2.5.1 Installation position and mounting .........................
Page 6
Table of figures Table of figures Fig. 1-1: 15.6" Prime Panel Performance Installation - view of device ................. 1 Fig. 1-2: 18.5" Prime Panel Performance Installation - view of device ................1 Fig. 1-3: 21.5" Prime Panel Performance Installation - view of device ................. 2 Fig.
Characteristic Characteristic Overview The Prime Panel Performance Installations with mITX-Core are designed as industrial touchscreens for demanding ap- plications with high connectivity. They are designed to be fitted into systems that are enclosed at the back (e. g. control cabinets, switchboards, etc.) and intended for the use in plant engineering. Protection class: IP65 at the front (not evaluated by UL), compliant with EN 60529 when properly fitted ...
Installation Installation Unpacking and checking delivery contents Check packaging for transport damage. – – Carefully remove the packaging to avoid causing damage. Keep the original packaging for future transport. Keep the documents supplied. – Check the contents of the packaging for visible transport damage. Check the contents for completeness on the basis of the delivery bill.
Installation Ventilation Cooling concept • The processor is cooled purely passively via free convection, i.e. neither CPU nor system fans are used. • The CPU as well as all power semiconductors of the power supply are connected to the cover of the computer housing via heatspreaders and heatpipes.
Installation 2.5.1 Installation position and mounting The device is designed for horizontal installation (connections at bottom). Vertical installation as well as deviations of up to ±5° from the specified directions are permissible. If deviating from the vertical installation, make sure not to cause a heat build-up inside the device. ...
Installation 2.5.3 Fastening and sealing The device is suitable for installation in the front panels of suitable housings, such as control cabinets, consoles, racks and hinged frames. Use an installation cut-out that provides bracings in the housing for stabilization. Install such bracings where necessary.
Installation 2.5.5 Installation in 19" cut-out using mounting clamps and mounting plates (18.5" display only) It is possible to install the 18.5" display in a 19" cut-out. In this case, the 4 lateral mounting clamps are replaced with 4 mounting plates with grub screws. The mounting plates are fastened to lateral U rails in the 19"...
Installation 2.5.6 Installing the mounting clamps After inserting the device into the front plate of the housing, use the provided mounting clamps to fasten it to the housing. To do so: – Place the provided mounting clamps on the front plate and snap them into the designated slots on the device. –...
Installation 2.5.7 Installing mounting clamps and mounting plates After inserting the device into the installation cut-out, use the provided mounting clamps and mounting plates to fasten it. To do so: – Place the provided mounting clamps on the control cabinet wall and snap them into the designated slots on the device.
Connection, commissioning and operation Connection, commissioning and operation Establishing operational readiness Interference-free connections for trouble-free operation When connecting peripheral devices, use shielded bus and LAN cables with shielded connectors to meet EMC requirements. If possible, screw or lock the plug connections as this will improve electrical shielding Signal lines must not be routed in the same cable duct as power lines.
Never operate the Prime Panel Performance Installation with the housing open. Preconditions The devices from Schubert System Elektronik GmbH feature peripheral interfaces that can be used to connect various components. When using commercially available peripheral devices (e.g. at the USB port), please note that their EMC interference immunity is often designed for office use.
Connection, commissioning and operation Opening and closing the device 3.3.1 Parts of the device Computer housing Front-end Cover plate Glass front Heat sink Mounting clamp EMC seal Front pan Sealing Fig. 3-1: Parts of the device The device consists of the front-end and the computer housing. The two components are screwed together. Front-end ...
Connection, commissioning and operation 3.3.2 Opening the device Damage to the device To avoid damage to the device, perform the following before opening it: Shut down the operating system. – – Disconnect the power supply. Damage to the display Always use a suitable soft, clean pad to set the device down on; otherwise, the display may get scratched.
Connection, commissioning and operation 3.3.3 Closing the device Damage to the display Always use a suitable soft, clean pad to set the device down on; otherwise, the display may get scratched. Fig. 3-3: Closing the device Carefully set the display down on a suitable soft, clean pad. –...
Connection, commissioning and operation Connecting the power supply Supply voltage 24 V DC Electric shock if unsuitable power supply is used. Connect the device only to a 24 V DC power supply that meets the requirements for safe extra-low voltage (SELV) according to EN/UL 61010-2-201. Connect the device only to a 24 V DC power supply that meets the requirements for an energy-limited circuit according to EN/UL 61010-1, chapter 9.4 or to a circuit that meets the requirements of NEC Class 2 according to UL 1310.
Connection, commissioning and operation Connecting peripheral devices 3.5.1 Interfaces Access to connections and drives Connections to the peripherals are located on the side of the computer housing. For more details on the connections, see chapter “4 Technical data” on page 20. Fig.
CFast memory card Fig. 3-6: Replacing CFast storage media 3.6.3 Operating system As ordered, Schubert System Elektronik GmbH installs the operating system specified in chapter “4 Technical data” on page 20. License notice: The pre-installed operating system is software in the Microsoft Embedded license model.
Connection, commissioning and operation 3.6.5 Replacing the buffer battery Fire and explosion hazard of the battery. The battery may explode if not handled according to instructions! Do not recharge, disassemble or dispose of in fire! The lithium battery may only be replaced by a type approved by the manufacturer. ...
Connection, commissioning and operation Installing the buffer battery Insert the new buffer battery into the socket with “+” facing upwards. To do this, first insert the buffer battery on the side opposite the clamp under the holders. Then press the buffer battery down until the clamp fixes the buffer battery in the socket. Fig.
Technical data Technical data General data for all Prime Panel Performance Installation 15.6" / 18.5" / 21.5" Component Description Housing • Aluminum front frame, powder-coated • Steel plate back wall, galvanized • Aluminum computer kernel with heat sink, anodized • Tempered anti-glare front glass. •...
Page 27
Technical data Storage temperature -20 °C to +60 °C Air humidity 10 % to 80 %, non-condensing Altitude Max. 2000 m Degree of pollution EMC immunity Industrial environment according to EN 61000-6-2 EMC emitted Industrial environment according to EN 61000-6-4 interference Shock 15 g: 11 ms and 25 g: 6 ms according to EN 60068-2-27...
Technical data 4.1.1 15.6" Prime Panel Performance Installation Component Description Model code PPI1000ED_156 Display • 15.6" Full-HD display, 1920 x 1080 pixels, 16:9, optional HD resolution • 450 cd/m brightness • Contrast ratio: 800 • View angle: 85/85/85/85° • Service life of lighting: min. 50,000 h Current consumption 3.2 A Dimensions...
Ground straps with ring cable lugs are not suitable. The grounding point must also have a low-impedance ground connection. Length, width and shape of the ground straps are recommendations of Schubert System Elektronik GmbH. Fig. A-2: Ground straps Grounding concept Annex | V 1.02...