1
Maintenance
Maintenance and annual startup
Table 1B Service and Maintenance Schedules
General:
• Address reported problems
• Inspect interior; clean and vacuum if necessary
• Check for leaks (water)
• Check system water pressure/system/piping/expansion tank
• Check fill water meter
• Test boiler water. When test indicates, clean system water with approved system
restorer following manufacturer's information
• Check control settings
• Check wiring and connections
⚠
If this boiler may be frozen, immediately shut off power to the appliance and contact the factory for further
DANGER
instructions. Operation when the pressure vessel, internal pipes, or pressure relief valves are frozen, will result
in internal pressure build-up and a deadly steam explosion. Neither the Freeze Protection feature of the boiler
control module, nor the use of glycol eliminates the possibility of freezing.
⚠
Follow the Service and maintenance procedures given throughout this manual and in component literature
WARNING
shipped with the boiler. Failure to perform the service and maintenance could result in damage to the boiler or
system. Failure to follow the directions in this manual and component literature could result in severe personal
injury, death, or substantial property damage.
⚠
The boiler should be inspected annually only by a qualified service technician. In addition, the maintenance and
WARNING
care of the boiler designated in Table 1A and Table 1B, and explained on the following pages must be performed
to assure maximum boiler efficiency and reliability. Failure to service and maintain the boiler and system could
result in equipment failure.
⚠
Electrical shock hazard – Turn off power to the boiler and disconnect the main feed before any service operation
WARNING
on the boiler except as noted otherwise in this instruction manual. Failure to turn off electrical power could
result in electrical shock, causing severe personal injury or death.
Address reported problems
Inspect any problems reported by the owner and correct before
proceeding.
Inspect boiler area
Verify that boiler area is free of any combustible materials,
gasoline and other flammable vapors and liquids.
Inspect boiler interior
1. Open the top panel and front door and inspect the interior
of the boiler.
2. Vacuum any sediment from inside the boiler and
components. Remove any obstructions.
Service technician
(see the following pages for instructions)
TM
Check all piping for leaks
⚠
Eliminate all system or boiler leaks.
WARNING
Continual fresh makeup water will reduce
boiler life. Minerals can build up in sections,
reducing heat transfer, overheating pressure
vessel, and causing pressure vessel failure.
Leaking water may also cause severe property
damage and risk of electrocution.
1. Inspect all water piping and verify to be leak free.
2. Look for signs of leaking lines and correct any problems
found.
User's Information Manual
5
Need help?
Do you have a question about the LECTRUS KEB0015 and is the answer not in the manual?