Appendix A (configuration instructions)
16.2.8
Remote operation
Apart from measuring the room temperature, the Types 5257-5
Panels (Pt1000 sensor) as well as Type 5244
ing opportunities of influencing the control process:
Selecting the operating
mode:
Set point correction:
No longer available
1)
With an activated room sensor, the measured room temperature is displayed when the re-
mote operation is connected and activated. Nevertheless, it is not used for control when ei-
ther the optimization, adaptation or flash adaptation function is activated.
Functions
Room sensor RF1/RF2
16.2.9
Optimization
This function requires the use of a room sensor. Depending on the building characteristics,
the controller determines and adapts the required advance heating time (maximum 8 hours)
to ensure that the desired 'Day set point' (rated room temperature) has been reached in the
reference room when the time-of-use starts. During the advance heating period, the controller
heats with the max. flow temperature. This temperature is built up in steps of 10 °C. As soon
as the 'Day set point' has been reached, outdoor-temperature-compensated control is activat-
ed.
Depending on the room sensor, the controller switches off the heating system up to one hour
before the time-of-use ends. The controller chooses the deactivation time such that the room
temperature does not drop significantly below the desired value until the time-of-use ends.
During the advance heating period and the premature deactivation of the heating system, the
or
icon blinks on the display.
Outside the times-of-use, the controller monitors the 'Night set point' (reduced room tempera-
ture). When the temperature falls below the night set point, the controller heats with the max.
flow temperature until the measured room temperature exceeds the adjusted value by 1 °C.
16-48
Room Panel (PTC sensor) provide the follow-
1)
Automatic mode
Day mode
Night mode
During rated operation, the room temperature set point can be
increased or reduced by up to 5 °C using a continuously adjustable
rotary knob.
Default
Configuration
0
CO1, 2 -> F01 - 1
and Type 5257-51 Room
1)
EB 5573 EN