SEM1605THV USER GUIDE
SMART RAIL MOUNT THERMISTOR TRANSMITTER
THREE WIRE (0 to 10) V OUTPUT
Important - Please read this document before installing.
Every effort has been taken to ensure the accuracy of this document; however, we do
not accept responsibility for damage, injury, loss or expense resulting from errors and
omissions, and we reserve the right of amendment without notice.
IMPORTANT – CE, UKCA & SAFETY REQUIREMENTS
Product must be mounted inside a suitable enclosure providing environmental
protection to IP65, higher is recommended.
To maintain CE, UKCA EMC requirements, input wires are recommended to be less
than 30 metres.
The product contains no serviceable parts, or internal adjustments. No attempt must
be made to repair this product. Faulty units must be returned to supplier for repair.
This product must be installed by a qualified person. All electrical wiring must be
carried out in accordance with the appropriate regulations for the place of installation.
Before attempting any electrical connection work, please ensure all supplies are
switched off.
ABSOLUTE MAXIMUM CONDITIONS (To exceed may cause damage to the unit).
Supply Voltage
± 30 V dc (Protected for over voltage and reverse
connection) SELV
Current with overvoltage
± 200 mA
Input Voltage
± 3 V between any terminals
Ambient
Temperature (- 30 to 70) °C
RH (10 to 95) % non-condensing
---------------------------------------------------------------------------------
1~DESCRIPTION.
The SEM1605THV is a cost-effective digital rail mount transmitter that accepts
Thermistor temperature sensors and converts sensor output over a configured range
to a standard industrial (0 to 10) V transmission signal.
2~RECEIVING AND UNPACKING.
Please inspect the packaging and instrument thoroughly for any signs of transit
damage. If the instrument has been damaged, please notify your supplier immediately.
3~SPECIFICATION.
Refer to data sheet for full specification. Download at
Configuration
Factory default
YSI10KB (-55 to 205) °C, upscale burnout, 0.0°C offset
4~INSTALLATION AND WIRING
Important safety requirements
This equipment is suitable for environment Installation BS EN61010-
1 Pollution Degree 2; Installation CAT II; CLASS I and is classed as
"PERMANENTLY CONNECTED EQUIPMENT". The equipment is
intended for industrial and commercial application only and not
suitable for domestic or medical use.
The equipment must be mounted inside an enclosure that provides
protection >= IP65. In NORMAL USE, the equipment will only be
accessed for maintenance by qualified personnel. Please ensure the
equipment is mounted vertically with terminals (7 and 8) at the
bottom. This will provide maximum ventilation. This equipment may
generate heat. Ensure the enclosure size is adequate to dissipate
heat. Be sure to consider any other equipment inside the enclosure.
The equipment surfaces may be cleaned with a damp cloth. Use a
mild detergent/water. Ensure the supply is OFF before cleaning and,
on completion of cleaning, the equipment is completely dry before
the supply is turned back ON.
This equipment must be installed by a qualified person. All electrical
wiring must be carried out in accordance with the appropriate
regulations for the place of installation.
D2675-01-01
Important – Read this
document before installing.
www.status.co.uk
4.1~MECHANICAL.
Dimensions in mm
The equipment must be mounted on a DIN rail style DIN EN50022
inside a plastic or metal enclosure with a protection level >= IP65. All
wiring must be secured. Maximum cable sizes 2.5 mm². Connection
is via screw clamp terminals.
4.2~ELECTRICAL
CONNECTIONS. For wiring connections refer to the side label on the
SEM1605THV and this document
4.2.1~OUTPUT: connections for cable length >3 metres, use
screen or twisted pair cables.
Always ensure the output (0 to 10) V is grounded at one point; this
would normally be at the monitoring equipment or power supply.
Screened wires are recommended for output wires. Avoid running
signal wires alongside mains or AC power lines or other sources of
electrical interference.
Pin 1 = Supply 0 V (-)
Pin 2 = Supply Positive V (+), (15 to 30) Vdc
Pin 4 = Output Signal (0 to +10) V
4.2.2~INPUT
length and type and as short as possible.
Note: Tested with 30-metre input sensor wires to
meet BS EN 61326, keeping cable within this length
is recommended.
2 Wire Thermistor and RTD sensor connection
Pin 5
Pin 7
Thermistors polarity is not required.
If no sensor (input) connection is made, the transmitter will go to its
error signal output value, depending on configuration.
4.3~S LED (STATE)
The State LED is OFF under normal run conditions indicating an in-
range input signal. If the input signal is out of range or is lost, the
State LED will light (RED)
The State LED also has some programming functions. See 5.2
.
:
Thermistor wires should be equal

Advertisement

loading
Need help?

Need help?

Do you have a question about the SEM1605THV and is the answer not in the manual?

Questions and answers

Summary of Contents for Status SEM1605THV

  • Page 1 1~DESCRIPTION. 4.2.2~INPUT Thermistor wires should be equal The SEM1605THV is a cost-effective digital rail mount transmitter that accepts length and type and as short as possible. Thermistor temperature sensors and converts sensor output over a configured range to a standard industrial (0 to 10) V transmission signal.
  • Page 2 A digital voltmeter connected to the output of the Live data can be displayed showing input and output values. This SEM1605THV will be useful to monitor the (0 to 10) V output can only be done if the device is powered as well as connected to signal.