ATTENTION : La pression d’alimentation maximale est de 120 PSI. L’air soufflé doit être propre, sec et exempt d’huile conformément à la norme ANSI / ISA-7.0.01-1996 ou BS ISO 8573-1 :2010. CRANE Co. 280N MIDLAND AVENUE, STE.258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 4/19/2024 TECH-566/ D.W.O.
For 24 VDC service below 1 watt, R (Rhodium Magnum switches) is recommended For 24 VDC service below 1 watt, T (Tungsten Magnum switches) is recommended CRANE Co. 280N MIDLAND AVENUE, STE.258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com...
Step 4. Ensure proper axial alignment between unit shaft, coupler and actuator shaft. Step 5. Failure to ensure alignment could result in long-term stress-related failure of unit shaft in high cycle or high torque applications. CRANE Co. 280N MIDLAND AVENUE, STE.258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 4/19/2024 TECH-566/ D.W.O.
Standard flow manifold comes with a choice of ¼ NPT, or ¼ BSP port sizes (See Figure 3). High Flow manifold comes with a choice of ⅜ NPT, or ⅜ BSP port sizes (See Figure 4). CRANE Co. 280N MIDLAND AVENUE, STE.258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com...
6 seconds, the function is canceled, and the LCD display reverts to opening percentage “xx%” If Auto-calibration is started by mistake, press again within 5 seconds to cancel auto calibration. CRANE Co. 280N MIDLAND AVENUE, STE.258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 4/19/2024 TECH-566/ D.W.O.
K20 comes as factory calibrated such that 4mA is the fail position and 20mA is the span position of the valve. An auto-calibration feature is available to tune the positioner to the automated valve package. CRANE Co. 280N MIDLAND AVENUE, STE.258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 4/19/2024 TECH-566/ D.W.O.
Page 14
First, follow the procedure for Auto-calibration. Next, set the loop current to the desired zero value. Press SEL until the display shows “LO CAL” then press CRANE Co. 280N MIDLAND AVENUE, STE.258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 4/19/2024 TECH-566/ D.W.O.
(M A N X X ). Depending on the actuator size and settings (ie. Drop Off), changing position may take longer, and may require multiple presses of Note: Figure 5 below displays how to navigate the Manual Mode menu CRANE Co. 280N MIDLAND AVENUE, STE.258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 4/19/2024 TECH-566/ D.W.O.
Press to increase the Gain o Press and hold to save. Note: Factory Default setting of the reverse gain is 10. CRANE Co. 280N MIDLAND AVENUE, STE.258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 4/19/2024 TECH-566/ D.W.O. 25330...
When drop off feature is enabled (LCD displays “ D R E N A B L ” ), the span- adjustment value will be overridden. CRANE Co. 280N MIDLAND AVENUE, STE.258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 4/19/2024 TECH-566/ D.W.O.
5.11 Calibration Timeout Setting There are two types of calibration timeout settings in K20 Series – Regular Calibration (REG CAL) and Long Calibration (LONG CAL). The default is REG CAL with optional LONG CAL required if the valve takes longer time (approx. > 30 seconds) to open, close, or shows friction during movement.
A discolored filter may also indicate the need for an evaluation of the air-supply quality. A filter/regulator with a 5 micron or better element, just prior to the positioner, is therefore recommended. CRANE Co. 280N MIDLAND AVENUE, STE.258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 4/19/2024 TECH-566/ D.W.O.
Error occurs within two minutes when performing an Auto-calibration for Low Current when the current is outside of the input current calibration range indicating that the loop current needs to be set to the desired Low Current value. CRANE Co. 280N MIDLAND AVENUE, STE.258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 4/19/2024 TECH-566/ D.W.O.
Page 26
"SENS ERR" Error occurs if we do not have communication with the detected sensor. "ERROR MAGNET PRESENT?" Error occurs when sensor's values do not change. CRANE Co. 280N MIDLAND AVENUE, STE.258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 4/19/2024 TECH-566/ D.W.O.
TO SELECT ACTUATOR DIRECTION ON AIR AND DISPLAY 0-100 or 100-0 READING. DIRECT OR REVERSE ACTING PRESS AND RELEASE SEL UNTIL 'DIR ACTG' OR 'REV ACTG' SHOWS IN THE DISPLAY. SELECT ACTUATOR OPERATION. CRANE Co. 280N MIDLAND AVENUE, STE.258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 4/19/2024 TECH-566/ D.W.O.
Page 30
R E G C A L R E S T O R E F A C T O R Y D E F A U L T ? CRANE Co. 280N MIDLAND AVENUE, STE.258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 4/19/2024 TECH-566/ D.W.O.
Page 31
C a l o r L o n g C a l o n A u t o C a l K20 HART DD Menu Structure CRANE Co. 280N MIDLAND AVENUE, STE.258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 4/19/2024 TECH-566/ D.W.O.
Read Long Tag Read Unique Identifier Associated with Long Tag Write Long Tag Reset "Configuration Changed" Flag Read Additional Device Status CRANE Co. 280N MIDLAND AVENUE, STE.258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 4/19/2024 TECH-566/ D.W.O. 25330...
Burst Mode This Field Device does not support Burst Mode. Catch Device Variable This Field Device does not support Catch Device Variable. CRANE Co. 280N MIDLAND AVENUE, STE.258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 4/19/2024 TECH-566/ D.W.O. 25330...
Read Last Calibration Info Send Abort Calibration Set Device ID – Unpublished command, Manufacturer use only to set Device ID. Used by device, not DD. CRANE Co. 280N MIDLAND AVENUE, STE.258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 4/19/2024 TECH-566/ D.W.O.