    Fireplaces equipped with a water boiler must be pressure-tested after hydraulic connection to the heating system. Masonry work may follow only after this pressure test. Ulrich Brunner GmbH does not cover any costs incurred by necessary dismantling of masonry for rework at water boiler installation or replacement of the boiler.
  • Page 3: Safety Precautions

    If additional parts are installed on the fireplace which are not approved for this appliance by Ulrich Brunner GmbH (for example, an external control unit), it is a customized product that meets cus- tomer requirements. The resulting fireplace insert is not type-tested; the declaration of performance of this fireplace insert will be no longer valid.
  • Page 4: Equipotential Bonding And Lightning Protection

    EN 13229 and bear the type designation EN 13229 W. Combustion air is supplied through a provided connecting piece. The volume of air supplied for combustion can be controlled by using a combustion air regulator. Installation Guide Kompakt-Kessel (1.37) © 2023 Brunner GmbH...
  • Page 5: Delivery Content

    00721 Return increase - thermal valve (when not using the pump group item no. 00717) Art.Nr.: 11726 Conversion kit for cleaning B4 front Art.Nr.: 11727 Conversion kit for cleaning B4 on side © 2023 Brunner GmbH Installation Guide Kompakt-Kessel (1.37)
  • Page 6: Description Of Connections

    Where sufficient volume of combustion air is not guaranteed. Where flammable materials or explosives are stored, manufactured or processed. Which are commonly accessible. Stairways in residential buildings with access from only two flats are not considered as commonly accessible rooms. Installation Guide Kompakt-Kessel (1.37) © 2023 Brunner GmbH...
  • Page 7 - If the construction type or dimensioning of the systems are excluding the possibility of dangerous negative pressure. Please consult the location of your fireplace, chimney connection and combustion air supply with your local chimney sweep. © 2023 Brunner GmbH Installation Guide Kompakt-Kessel (1.37)
  • Page 8: Combustion Air

    Combustion air ducts Stoves and fireplaces with BRUNNER heating inserts are classified by law as indoor air-dependent fire- places. The combustion air can be supplied from outside via a sufficiently dimensioned pipework. This for BRUN- NER heating inserts are fitted with a combustion air connection piece.
  • Page 9: Chimney And Smoke Pipe Connection

    CE mark. The connecting pipe must be connected directly to the chimney. A soot fire resistant chimney of T400 type is necessary for safe operation. All smoke pipe connections must be sealed tightly! Remember to provide access for cleaning! © 2023 Brunner GmbH Installation Guide Kompakt-Kessel (1.37)
  • Page 10: Assembly

    When delivered, this can be reached and operated via a warm air grille or similar installed above the combustion door (see variant 1). Im. 1: Cleaning aid B4 variant 1 Installation Guide Kompakt-Kessel (1.37) © 2023 Brunner GmbH...
  • Page 11 The installation of a heating flap is necessary for the B4 with an adjoining post-heating surface Adjustment of primary and secondary air The combustion air is adjusted at the factory. However, should a readjustment be necessary. so note the fol- lowing information. © 2023 Brunner GmbH Installation Guide Kompakt-Kessel (1.37)
  • Page 12 The combustion air supply required for the operation of the fireplace must be ensured. This is particularly im- portant with very airtight windows or ventilation systems. If necessary, provide a room air-independent com- bustion air duct (outside air supply to the combustion air socket). Installation Guide Kompakt-Kessel (1.37) © 2023 Brunner GmbH...
  • Page 13 Before using the compact boiler for the first time, make sure that the edge protection on the front window has been removed. Deduct if necessary. Be sure to observe the additional information in the installation and operating instructions! © 2023 Brunner GmbH Installation Guide Kompakt-Kessel (1.37)
  • Page 14: Adjusting The Combustion Door

    To be able to remove the combustion door, it is necessary to dismantle the panel. To do this, loosen the four screws of the panel fastening and pull off the panel. See also the assembly instructions for the stove or the assembly instructions for the panel. Installation Guide Kompakt-Kessel (1.37) © 2023 Brunner GmbH...
  • Page 15 In order to be able to remove the door, it is necessary to dismantle the frame. To do this, loosen the four screws on the frame fastening and pull off the frame. See also the assembly instructions for the fireplace stove or the assembly instructions for the frame. © 2023 Brunner GmbH Installation Guide Kompakt-Kessel (1.37)
  • Page 16: Installation Of Combustion Air Control Element For Manually Operated Stoves

    (see arrow on the picture in the middle of page) from the sliding plate. Now attach the control element as shown in the low- er picture and put the warning plate in place again. Check function! Installation Guide Kompakt-Kessel (1.37) © 2023 Brunner GmbH...
  • Page 17: Overview Of Fire Safety And Protection Of Other Structures Against Heat

    Installation in front of or next to an adjacent wall Installation in front of or next to a flammable wall (U val- (U value ≥0.4W/m²K): ue ≤0.4W/m²K): Im. 12: Basic principles of fire safety and heat insulation © 2023 Brunner GmbH Installation Guide Kompakt-Kessel (1.37)
  • Page 18 Furniture or flammable objects on adjacent wall Air cooled heat protection Distance between floor insulation and air intake Decorative beam over fireplace door Thermal insulation of the smoke pipe connecting piece Heat radiation range Installation Guide Kompakt-Kessel (1.37) © 2023 Brunner GmbH...
  • Page 19: Mounting Instructions For Eas / Eos Variants

    • If possible, avoid installation of electronic components in exterior walls to prevent risk of corrosion at tem- peratures below dew point. • The control unit must not be installed in hot parts of the tiled stove casing. © 2023 Brunner GmbH Installation Guide Kompakt-Kessel (1.37)
  • Page 20: Building Protection

    - other walls (35), these are: walls from mineral building materials, such as aerated concrete, bricks, sand- lime bricks, with thickness of more than 10 cm (3.94 in). For these walls, the insulation layer (32) is enough; a brick lining (33) is not necessary. Installation Guide Kompakt-Kessel (1.37) © 2023 Brunner GmbH...
  • Page 21 - in front of the fireplace = at least 50 cm (19.69 in) - on both sides of the fireplace = at least 30 cm (11.81 in) above the fireplace door opening © 2023 Brunner GmbH Installation Guide Kompakt-Kessel (1.37)
  • Page 22: Approved Insulation Materials

    DIBt (Deutsches Institut für Bautechnik) might be used. For necessary insulation thicknesses please refer to the manufacturer's specifications. Insulation material rating for mineral wool according to AGI Worksheet Q 132: Installation Guide Kompakt-Kessel (1.37) © 2023 Brunner GmbH...
  • Page 23: Directives

    List of technical building regulations DIN EN 12831 Calculation of the standard heating load DIN EN 12828 Heating systems in buildings DIN EN 14597 Temperature control devices and limiters for heat generating systems © 2023 Brunner GmbH Installation Guide Kompakt-Kessel (1.37)
  • Page 24 Technical rules for drinking water installations In addition, it is necessary to observe the local building law and regulations for heating systems valid in your country. The listing does not claim to be complete! Installation Guide Kompakt-Kessel (1.37) © 2023 Brunner GmbH...
  • Page 25: Drawings And Technical Data

    Dimension sheets - Kompakt-Kessel B4 TF1 FTAS supply 1“ext. th. return boiler 1“ext.th. drain 1/2“int. th. supply cooling pipe outlet ext.th. return cooling pipe outlet 1/2“ex- t.th. FTAS socket for thermal safety sensor int.th. socket 1/2“ for sensor int.th. socket 1/2“ for sensor int.th. …...
  • Page 26 Dimension sheets - Kompakt-Kessel B4 FTAS supply 1“ext. th. return boiler 1“ext.th. drain 1/2“int. th. supply cooling pipe outlet ext.th. return cooling pipe outlet 1/2“ex- t.th. FTAS socket for thermal safety sensor int.th. socket 1/2“ for sensor int.th. socket 1/2“ for sensor int.th. …...
  • Page 27 Dimension sheets - Kompakt-Kessel B4 We suggest for CAD planning Palette CAD. Permanent updated drawings: www.brunner.de Frames/ flue gas outlet connection/ combustion air supply connection/ front variants/ support bearing are marked in col- Stand: 2023-09-11...
  • Page 28 Planning and installation - Kompakt-Kessel B4 Tested according to EN 13229 W EN 13229 W Values measured at Rated power Practical avg. Data for functional demonstration Rated heat power 14.5 Room heating power Water heating power Fire wood volume kg/h Combustion performance 16.5 Flue gas mass flow...
  • Page 29 Dimension sheets - Kompakt-Kessel B7 supply 1“ext. th. return boiler 1“ext.th. drain 1/2“int. th. supply cooling pipe outlet ext.th. return cooling pipe outlet 1/2“ex- t.th. FTAS socket for thermal safety sensor int.th. socket 1/2“ for sensor int.th. socket 1/2“ for sensor int.th. socket 1/2“...
  • Page 30 Dimension sheets - Kompakt-Kessel B7 supply 1“ext. th. return boiler 1“ext.th. drain 1/2“int. th. supply cooling pipe outlet ext.th. return cooling pipe outlet 1/2“ex- t.th. FTAS socket for thermal safety sensor int.th. socket 1/2“ for sensor int.th. socket 1/2“ for sensor int.th. socket 1/2“...
  • Page 31 Dimension sheets - Kompakt-Kessel B7 Design characteristics for adjacent storage mass We suggest for CAD planning Palette CAD. Permanent updated drawings: www.brunner.de Frames/ flue gas outlet connection/ combustion air supply connection/ front variants/ support bearing are marked in col- Stand: 2023-09-11...
  • Page 32 Planning and installation - Kompakt-Kessel B7 Tested according to EN 13229 W EN 13229 W Values measured at Rated power Practical avg. Data for functional demonstration Rated heat power Fire wood volume kg/h Combustion performance Flue gas mass flow 10.9 17.9 Outlet temperature (before reheating surface) °C...
  • Page 33 Dimension sheets - Kompakt-Kessel B8 supply 1“ext. th. return boiler 1“ext.th. drain 1/2“int. th. supply cooling pipe outlet ext.th. return cooling pipe outlet 1/2“ex- t.th. FTAS socket for thermal safety sensor int.th. socket 1/2“ for sensor int.th. socket 1/2“ for sensor int.th. socket 1/2“...
  • Page 34 Dimension sheets - Kompakt-Kessel B8 supply 1“ext. th. return boiler 1“ext.th. drain 1/2“int. th. supply cooling pipe outlet ext.th. return cooling pipe outlet 1/2“ex- t.th. FTAS socket for thermal safety sensor int.th. socket 1/2“ for sensor int.th. socket 1/2“ for sensor int.th. socket 1/2“...
  • Page 35 Dimension sheets - Kompakt-Kessel B8 We suggest for CAD planning Palette CAD. Permanent updated drawings: www.brunner.de Frames/ flue gas outlet connection/ combustion air supply connection/ front variants/ support bearing are marked in col- Stand: 2023-09-11...
  • Page 36 Planning and installation - Kompakt-Kessel B8 Tested according to EN 13229 W EN 13229 W Values measured at Rated power Practical avg. Data for functional demonstration Rated heat power Fire wood volume kg/h Combustion performance 15.8 22.5 Flue gas mass flow 11.3 18.9 Outlet temperature (before reheating surface)
  • Page 37 Zellhuber Ring 17-18 misprints reserved. D-84307 Eggenfelden Reprinting and reproduction, even in part, only with the express permission of the publisher. Tel.: +49 (0) 8721/771-0 / Fax: +49 (0) 8721/771-100 Email: info@brunner.de Art.Nr.: 19908 © 2023 Brunner GmbH Installation Guide Kompakt-Kessel (1.37)