NK TECHNOLOGIES ATPR Series Instructions

Powered rms ac current transducers 0-200a input maximum range 0-5vdc or 0-10vdc output

Advertisement

Quick Links

Specifi cations
Output Signal
0-5VDC or 0-10VDC proportional to
the RMS Current
Output Limit
112% of standard output range
maximum value
Frequency Range
10-400 Hz
Response Time
( 90% of step change) 600mS
Accuracy
1.0% Full Scale Split Core
100K Ω Minimum
Loading
Power Supply
24VDC
See "Output Wiring" section.
Isolation Voltage
UL listed to 1,270VAC, tested to
5kV
Case
UL 94V-0 Flammability rated
thermoplastic
Environmental
-20 to 50 Deg. C, (-4-122 Deg F)
0-95% RH, non-condensing
Listing
Designed to meet CE, UL 508
Industrial Control Equipment
Input Maximums
MAXIMUM INPUT AMPS
MODEL RANGE 6 SEC.
ATPR0
0-2A
125
ATPR0
0-5A
125
ATPR1
0-10A
125
ATPR1
0-20A
150
ATPR1
0-50A
215
ATPR2
0-100A
300
ATPR2
0-150A
450
ATPR2
0-200A
500
Model Number Key
ATP R 1 - 010 - 24D - SP
OUTPUT:
005- 0-5VDC
010- 0-10VDC
RANGE
0 - 2 & 5 Amps
1 - 10, 20 or 50 Amps
2 - 100, 150 or 200 Amps
SENSOR TYPE:
ATPR - True RMS AC current transducers, 24VDC
powered 0-5 or 10VDC output.
Know Your Power
Other NK Technologies Products Include:
1 SEC.
AC & DC Current Transducers
250
AC & DC Current Operated Switches
250
1φ & 3φPower Transducers
Current & Potential Transformers (CTs&PTs)
250
300
400
600
800
3511 Charter Park Drive, San Jose CA 95136
1,000
800-959-4014 or +1-408-871-7510 Phone
+1-408-871-7515 FAX
sales@nktechnologies.com, www.nktechnologies.com
CASE STYLE
SP- Split Core
POWER SUPPLY:
24D- 24VDC with non-isolated output
INSTRUCTIONS
ATPR SERIES
Powered RMS AC Current Transducers
0-200A Input Maximum Range
0-5VDC or 0-10VDC Output
Quick "How To" Guide
1. Run the wire you are monitoring through aper-
ture.
2. Mount the sensor to a surface if needed.
3. Connect output wiring.
A. Use up to 14AWG copper wires.
B. 0-5/10 VDC Models: Make sure output load
is at least 100 KΩ to achieve stated accuracy
4. Chose correct range by positioning the Range
Jumper.
5. Energize the sensor by connecting 24 VDC to the
power supply terminals.
ATPR Inst. Rev 1, 10/12 P/N 292000503