Contactors/Auxiliary Contacts
A1
M 3,5
1 Nm -
9 Ib.in
A2
M 3,5
0.3 Nm -
2.6 Ib.in
To be installed in environmental conditions pollution degree 3 or lower.
4x M4
30 mm
> 5 mm
100 mm
1,5 Nm - 13 lb.in
According to UL 60947-4-1:
Use wire Cu 75°C only. Use built-in cable clamps or use Listed (ZMVV) Wire Connectors and Soldering Lugs. Wire connectors
(Cable pole-shoe) crimped with special factory crimp tool. Enclosure with min. dimension 24 by 20 by 10 inches should be used.
AF(S)116-30, AF(S)140-30, AF(S)146-30: Suitable for use on a circuit capable of delivering not more than the max. symmetrical
amperes at the max. voltage, shown in SOC.
Only use wires of the same
dimension when you connect 2
wires to each terminal.
4 mm
M8
8Nm - 71 Ib.in.
ø 5,5
Pz 2
1 x 1 ... 4 mm²
2 x 1 ... 4 mm²
1 x AWG 18 ... 14
2 x AWG 18 ... 14
1 x 0.2 ... 1.5 mm²
ø 3,5
2 x 0.2 ... 1 mm²
1 x AWG 24 ... 12
2 x AWG 24 ... 12
4x M4
60 mm
> 5 mm
100 mm
Pz 2
1,5 Nm - 13 lb.in
Flexible
1 x 0,75 ... 2,5 mm²
1 x 0,75 ... 2,5 mm²
2 x 0,75 ... 2,5 mm²
2 x 0,75 ... 2,5 mm²
1 x AWG 18 .. 14
2 x AWG 18 .. 14
1 x 0,2 ... 2,5 mm²
1 x 0,25 ... 2,5 mm²
2 x 0,2 ... 1,5 mm²
2 x 0,25 ... 1 mm²
1 x AWG 24 ... 12
2 x AWG 24 ... 12
30°
Pos 1 ± 30°
20 mm/0,78"
1 x 10...95 mm²
2 x 10...95 mm²
Stranded
1 x AWG 6...4/0
2 x AWG 6...4/0
1 x 10...70 mm²
2 x 10...70 mm²
1 x 0,75 ... 2,5mm²
2 x 0,75 ... 2,5mm²
1 x 0,25 ... 2,5 mm²
2 x 0,5 ... 1,5 mm²
Pos 2
30°
Pos 4
Pos 3
Pos 1
AF(S)116(B)-30(RT), AF140(B)-30(RT),
AF(S)146(B)-30(RT)
LL146-30
6x
M6
6x
M6x20
6x
6.4x14
AF116(B)-40(RT), AF140(B)-40(RT)
LL146-40
8x
M6
8x
M6x20
8x
6.4x14
9 mm
I > 3,5 mm
L < 8 mm
6 mm
Pos. 5
LD146-30
2x
LD146-40
2x
20 mm
(0,78")
5,5 mm
(0,22")
22 mm
(0,86")
5 mm
M6
9 Nm - 80 Ib.in.