Download Print this page

Olimpia electronics GR-1936/15L/ML Quick Start Manual

Waterproof non maintained/maintained emergency luminaires with white leds

Advertisement

Quick Links

A-1900
Test card
LED MODULE CHARACTERISTICS
Manufacturer
Model Number
Voltage Range
Nominal Power
Connections
Non reversible connection between main pcb and led module
Temperature (tc)
WARRANTY
Olympia Electronics guarantees the quality, condition and operation of the goods. The period
of warranty is specified in the official catalogue of Olympia Electronics and also in the
technical leaflet, which accompanies each product. This warranty ceases to exist if the buyer
does not follow the technical instructions included in official documents given by Olympia
Electronics or if the buyer modifies the goods provided or has any repairs or re-setting done
by a third party, unless Olympia Electronics has fully agreed to them in writing. Products that
have been damaged can be returned to the premises of our company for repair or
replacement, as long as the warranty period is valid.
Olympia Electronics reserves the right to repair or to replace the returned goods and to or not
charge the buyer depending on the reason of defection. Olympia Electronics reserves the
right to charge or not the buyer the transportation cost.
HEAD OFFICE
72nd km. O.N.R. Thessaloniki-Katerini
P.C. 60300 P.O. Box 06 Εginio Pierias Greece
www.olympia-electronics.com
info@olympia-electronics.gr
Page 4 from 4
Manual TEST with the A-1900 Test
card (not included). This card is
available only after request. In order to
test the device, you must place the
card on the side of the indications.
This operation lasts as long as the
card is present.
GR-1936/15L/ML
Olympia Electronics S.A.
2502159/15L
2.9-3.6 V DC
980mw
47 °C max. across the board
923193604_09_001
WATERPROOF NON MAINTAINED / MAINTAINED EMERGENCY LUMINAIRES WITH WHITE LEDs
TECHNICAL CHARACTERISTICS
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERIES (Ni-Cd)
BATTERY PROTECTION
INDICATIONS
CHARGING TIME
MINIMUM AUTONOMOUS DURATION
ILLUMINATION SOURCE
ILLUMINATION (MAINS / EMERGENCY)
DEGREES OF COVER PROTECTION
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIALS
EXTERNAL DIMENSIONS
TYPICAL WEIGHT
GUARANTEE
Thank you for your trust in our products.
Olympia Electronics - European manufacturer.
GENERAL
These luminaires are used where emergency light is needed. Each luminaire must be permanently
connected to the mains power supply. In normal operation the battery is charging, the green LED
and 2 yellow LED's light in non-maintained operation. The green LED and the LED strip light in
maintained operation. In case of a mains power supply failure the luminaire will light the LED
strip automatically in emergency mode. When the mains power supply is restored the device
turns to normal operation.
Non maintained / maintained operation There is an option to select the non-maintained or
maintained operation by placing the jumper to the appropriate place (page 2).
INSTALLATION
To install the luminaire follow the installation instructions on page 2.
ΑΤΤΕΝΤΙΟΝ!!!
1. Operations for installation, maintainance or testing must be done by authorized personnel only.
2. The luminaire must be connected to the mains power supply through a fuse dependent on the
total amount of the line's power load.
3. It is suggested to check every month the indication LED for battery charging, and by placing the
test card
(A-1900)
(page 3) an operation test is initiated, to check the
emergency cirquit. The illumination source should light as long as the card is
condition contact the installer.
4. It is suggested to check every 6 months the minimum autononous duration by disconnecting the
mains power supply. Count the time that the led strip lights and in case of less time than the
minimum autonomous duration the battery must be replaced. If the measured time is considerably
less than the minimum autonomous duration
replacement, these must be replaced by parts of the same type, by the manufacturer or by a
competent person.
5. In case of inactive use for a period greater than 2 months, disconnect the battery by pulling out the
battery's connector.
Page 1 from 4
(for LED MODULE Specs see page 4)
GR-1936/15L/ML
220-240V AC/50-60Hz
3.4W/3.6VA
3.6V/1Ah
From overcharge and deep discharge
Charge indication LED
24h
180min
15 white LEDs
50lm / 120lm
IP65
o
5 to 40 C
Up to 95%
ABS/PC, PC
313 x 118 x 66 mm
650gr.
3 years (1 year for the battery)
present. In the opposite
contact the installer.
In case of battery or led strip
923193604_09_001

Advertisement

loading

Summary of Contents for Olimpia electronics GR-1936/15L/ML

  • Page 1 Test card card on the side of the indications. This operation lasts as long as the card is present. TECHNICAL CHARACTERISTICS (for LED MODULE Specs see page 4) GR-1936/15L/ML OPERATION VOLTAGE 220-240V AC/50-60Hz MAXIMUM POWER CONSUMPTION 3.4W/3.6VA BATTERIES (Ni-Cd) 3.6V/1Ah...
  • Page 2 INSTALLATION INSTRUCTIONS FOR WALL OR CEILING MOUNTING 6. I s not allowed to discard batteries in to common trash bins, they must be discarded only in battery recycling points. Do not incinerate. 1. Unclip the plastic latches with a flat blade screwdriver, unfasten the 2 screws (not all the way, step 8 B) and remove the diffusor.