Haier AB36NACBEA Service Manual page 44

4hp 5hp universal outdoor unit air conditioning
Hide thumbs Also See for AB36NACBEA:
Table of Contents

Advertisement

5.3.2 Installation of outdoor unit
BE SURE TO READ THESE INSTRUCTIONS CAREFULLY BEFORE BEGINNING
INSTALLATION. FAILURE TO FOLLOW THESE INSTRUCTIONS COULD CAUSE SERIOUS
INJURY OR DEATH, EQUIPMENT MALFUNCTION AND/OR PROPERTY DAMAGE.
BE SURE TO READ INSTALLATION MANUAL FOR INDOOR UNIT WITH THIS MANUAL.
a. Accessories
"Edging" for protection of electric wires from an
opening edge.
b. Selection of the place of installation
Select the place of installation satisfying the following conditions and, at the same time, obtain
a consent from the client or user.
Place where air circulates.
Place free from heat radiation from other heat sources.
Place where drain water may be discharged.
Place where noise and hot air may not disturb the neighborhood.
Place where there is not heavy snowfall in the winter time.
Place where obstacles do not exist near the air inlet and air outlet .
Place where the air outlet may not be exposed to a strong wind.
Place surrounded at four sides are not suitable for installation. A 1m or more of overhead
space is needed for the unit.
Mount guide-louvers to place where short-circuit is a possibility.
When installing several units, secure sufficient suction space to avoid short circuiting.
(1) Open space requirement around the unit
•L
Air inlet
L
2
Air
inlet
Air outlet
(2) Installation where the area with strong winds.
Install the unit so that the air outlet section of the unit must NOT be faced
toward wind direction.
c. Installation of outdoor unit
(1) Installation
Fix the unit in a proper way according to the condition of a place where it is installed by referring to the following .
(a)
Concrete foundation
Anchor bolt
Note (1) Give enough room for the
concrete foundation to fix by anchor bolts.
Install the unit so that the angle of inclination must be less than 3 degrees.
<Heat Pump model/Cooling Only model >
3
Distance
•500
(Servicing
space)
•L
1
Unit
Concrete foundation
To fix by bolts
INSTALLATION INSTRUCTIONS
WARNING
Case
I
open
L
1
L
300
2
L
150
3
Note (1) Place the concrete foundation deep
enough.
Edging
Unit: mm
II
III
open
500
open
0
300
150
Foundation anchor
Unit

Advertisement

Table of Contents
loading

Table of Contents