5. Terminating devices connected to the RAK-STAR
Devices connected to the RAK-STAR require a 'STAR' termination if at the end of line on a
cable run, if a device is in between a run it should be set to 'NO TERM'.
No TERM: Both Jumpers are removed
When a device is not at the end of line.
STAR TERM: Jumper fitted across 2+3 and 5+6
When a device is at the end of line, in a RAK-STAR
System it must be STAR terminated.
TERM: Jumper fitted across 1+2 and 4+5
This is not used on the RAK-STAR; TERM is used
At each end of a Radial system.
RAK-STAR