Page 1
Reproduc�on of this manual, or any part thereof, in any form, without the prior permission of DEGA.CZ s.r.o. is prohibited DEGA CZ s.r.o. reserves the right to alter the specifica�ons of the hardware and software described in this manual at any time and without prior no�ce...
Replacement of the sensor module ............................7 Replacement of the ba�ery ..............................7 Connec�ng the transmitter via current loop to the controller DEGA UPA II/UPA III ............7 Connec�ng the sensor via RS485 to the controller DEGA UKA III/DEGA UPA III ..............7 Installa�on of wiring for RS485 and power supply .......................
Usethe transmi�er only with the appropriate cer�fied DEGAproducts The device is cer�fied as func�onally and technically qualified only with original "DEGA" accessories. In case of using the device with any other products, the manufacturer is not liable for any damages that may occur.
80-120 kPa Flow of ambient air: max. 2 m/s - flow directly to the sensor in not allowed Protec�on level with a cover: IP 54, with a DEGA WATER CAP IP 66 cover Loca�on: BE3N2 - explosive atmospheres - zone 2...
Series of detectors in poten�ally explosive atmospheres Type of detected gas Sensor type with linear output Second generation product with new DEGA design DEGANSx-ELII with anelectrochemical sensor They operate on the principle of change of electrical parameters on the electrodes stored in electrolyte, due to oxidation/reduc�on reactions of the detected gas on it's surface.
Jumper connector of Jumper connector of the Terminal block Terminal block RS485 B the terminal resistor communica�on protocol RS485 A RS485 (DEGA/MODBUS) DIP switch for the RS485 Programming Ba�ery CR2032 LCD display connector address connector Status LED Assembly and disassembly of the transmi�er Before assembling, read the valid installation standards EN 60079-29-2 (Selection, installa�on, use and maintenance of...
Connectingthe transmitter via current loopto the controller DEGAUPAII/UPA III Connect one transmitter to each channel of the controller as shown in the picture below. Connectingthe sensorvia RS485to the controller DEGAUKAIII/DEGA UPAIII Installation of wiring for RS485and power supply Wiring must be installed using bus topology and in compliance with the RS485 policy.
120R. Plug a jumper on the JP2 connector of the last device on the bus to include the 120R termina�ng resistor. In the default configura�on, the jumper connector is not plugged. Communicationprotocol switchDEGA/MODBUS Plugging a jumper in the JP1 connector will switch from the DEGA communica�on protocol to the MODBUS communication protocol. Transmitter functions The detector's motherboard is equipped by status LEDs, which help in detec�ng problems during the installa�on.
Operation, maintenance, inspectionand serviceof the transmitter 1. Usagelimits To maintain proper operation of the transmitter, it is necessary to respect the fact that step changes of humidity, condensation or rapid changes of pressure can cause incorrect indication of the measured value. Each sensing technology is suited for different methods of applica�on, as described below.
%DMV – lev el of lower explosion limit concentra�o n in % %obj – volume sample of gas – lower explosive limit of methane (4.4 % by volume) 4. Package content 1 x NS II body 1 x NS II sensor unit...
• contrary to the advice provided in the instruc�on manual DEGA products that have been used in associa�on with other than original DEGA products, including consumables and • accessories calibra�on of sensors ,i.e.se�ng detec�on limits...