Riello 3739750 Installation, Use And Maintenance Instructions page 39

Light oil burner
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 33
4.3 COMBUSTION HEAD SETTING
It depends on the output of the burner and is carried out by rotating clockwise or counterclockwise the set-
ting screw (6) until the set-point marked on the regulating rod (7) is level with the outside plane of the noz-
zle-holder assembly (1).
– In the sketch the combustion head is set for an output of 3.50 GPH at 15 bar.
The set-point 2.5 of the regulating rod is at the same level with the outside plane of the nozzle-holder assem-
bly as shown in the schedule.
4.4 ELECTRODES ADJUSTMENT (
ATTENTION
Lean the diffuser disc-holder as-
sembly (1) on the nozzle-holder
(2) and lock it by screw (3). For
prospective adjustments loosen
sc re w ( 4) and move the elec-
trodes assembly (5).
To have access to the electrodes
carry out operation as described in
chapter 4.2 (page 6) "RECOM-
MENDED NOZZLES".
4.5 PUMP PRESSURE AND AIR OUTPUT
st
1
STAGE ADJUSTMENT
ADJUSTMENT OF AIR SHUTTER:
Unloosen the nut (1), turn the screw (2) until the indicator (3) reaches the
position desired. Then lock the nut (1), (see Fig. 14).
PRESSURE REGULATION:
This is set at 9 bar at the factory.
Should it be necessary to re-set or alter such pressure, this can be done, by
adjusting screw (7).
The pressure gauge must be mounted in place of cap (8), (see Fig. 15).
2
nd
STAGE ADJUSTMENT
ADJUSTMENT OF AIR SHUTTER:
Unloosen the nut (4), turn the screw (5) until the
indica tor ( 3) re ache s th e po sit io n desir ed .
Then lock the nut (4), (see Fig. 14).
PRESSURE REGULATION:
T h i s i s s e t a t 1 4 b a r a t t h e f a c t o r y .
Should it be necessary to re-set or alter such pres-
sure, this can be done, by adjusting screw (9).
The pressure gauge must be mounted in place of
cap (8), (see Fig. 15).
When burner shuts down the air damper automati-
cally closes till a max. chimney depressure of
0,5 mbar.
2311
(see Fig. 12, page 6)
see Fig. 13)
Fig. 13
D5341
Fig. 15
7
GB
WARNING
MEASURES MUST BE
RESPECTED
Fig. 14