Detection Methods - UNI-T UT336A Quick Start Manual

Refrigerant leak detector
Hide thumbs Also See for UT336A:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
2) Buttons
Buttons
Short Press
Sensitivity
The detection
sensitivity is increased
Increase
/
POWER
Set the current gas
RESET
concentration to zero
The detection
Sensitivity
sensitivity is decreased
Decrease
MUTE
Buzzer ON/OFF
6. Operations
A. Basic Detection Flow
Install the
battery AA*4
as per the battery
polarity prompt
Long press
button to power
the device on
Adjust sensitivity
as needed:
Short press
or
button to adjust the
Device
sensitivity
warm-up (3s)
Reset as needed:
Short press
button
Detection
to set the current gas
concentration to zero
Be mute as needed:
Long press
Short press
button
button to power
to turn on/off the
the device off
buzzer
5
UT336A
Long Press
Lights
Green light is
/
on level by level
Full battery:
Backlight in Green
Power
Low battery:
Backlight in Red
on/off
Depleted battery:
Flashing in Red
Green light is
/
off after 2s on
Green light is
/
off level by level
/
/
1. Six green lights are
on level by level
then off, with Di
sound
2. Yellow/Orange/Red
lights are all on then
off, and reset as per
the startup gas
condition
3. Regular DiDi sounds
arise and the
backlight of POWER
button lights in green
Six green lights are
all on then off level
by level
UT336A
Notes:
a. The default sensitivity of device is level 3.
b. Short press the RESET button to set zero if it is alarming before the leak location
is detected.
c. When the refrigerant is detected, there will be with Di sound increasing in frequency,
and alarm lights in Yellow/Orange/Red are on level by level as per the leak
concentration.
B. Detection Methods
1. Visually inspect the refrigerating system to check if any oil and dust on the pipeline,
any leak on the valve, copper welding spot or pipeline.
2. Move the probe to carefully check every possible area, and the speed of moving
probe is ≤ 1cm/s, and the probe distance should be kept in 1-3mm. See followings:
3. ① Alarming of device identifies the approaching leak location, repeatedly detect
the surroundings to check if any repeat alarm occurred.
② When the leak location is ensured, move the probe from different directions
of non-alarm area to the alarm area to locate the leak source.
③ Move the device away from the leak area, then reset the device and gradually
decrease the sensitivity to repeatedly locate the concrete leak source.
④ Mark it down then go on the detection for other parts of the whole refrigerating
system when the leak location is concreted.