Installation, Operation & Maintenance Manual
Controller Status LED
The LED changes colour when the controller enters three (3) different states as follows.
Water On. Green LED remains illuminated when water is being supplied/valve is open (energised).
Fault. Amber LED remains illuminated when the rope fault is detected. Water supply will remain ON, BMS
terminal will switch over. Amber LED will turn Off and BMS terminal will switch back when rope fault has
been rectified. This feature is available only with 4 wire leak rope.
Alarm. Illuminated when water leak is detected. Water supply is Off (valve deenergised) until alarm
condition has been investigated, rectified, and reset. BMS and Strobe terminals will switch over.
Auto Reset
There is a switch on the circuit board labelled [AUTO RESET] which can be used to automatically reset Alarm
condition after water leak has been rectified (should only be used in conjunction with WLDZ2 or WLDZ4 panel).
Controller requires manual reset after Alarm (Default).
OFF
ON
Controller will reset automatically when Alarm condition is cleared.
Sensitivity
The potentiometer on the circuit board labelled [SENS] can be used to set the sensitivity of the rope sensor.
To increase the sensitivity, turn potentiometer clockwise towards MAX position.
To decrease the sensitivity, turn potentiometer anti-clockwise towards MIN position.
Basic Maintenance
Keep your gas controller in good working order - follow these basic principles.
Remove any dust/debris from the outer enclosure regularly using a slightly damp cloth.
✓
Never use detergents or solvents to clean your device.
✓
Never spray air fresheners, hair spray, paint or other aerosols near the device.
✓
Never paint the device.
✓
Rev 2
WLM
7