S&S Northern Merlin 1000S User Manual

Gas proving & detection system

Advertisement

Quick Links

Merlin 1000S
User Guide
Gas Safety Products
Merlin 1000S
Gas Proving & Detection System
User Guide
Please read this guide carefully and retain for future use.
Rev: 07
05-19
1

Advertisement

Table of Contents
loading

Summary of Contents for S&S Northern Merlin 1000S

  • Page 1 Merlin 1000S User Guide Gas Safety Products Merlin 1000S Gas Proving & Detection System User Guide  Please read this guide carefully and retain for future use.  Rev: 07 05-19...
  • Page 2: Table Of Contents

    Merlin 1000S User Guide Table of contents General Information ..................3 Panel Mounting ......................3 Circuit Board Terminals ..................4 POWER ........................... 4 GAS VALVE ........................4 BMS OUT ......................... 4 PRESSURE SENSOR ......................4 EM REMOTE ........................5 GAS DETECTOR ......................5 FS 1/2/3/4 ........................
  • Page 3: General Information

    General Information The Merlin 1000S is a gas proving and detection system. The system comprises of a control panel and a gas pressure sensor. The Merlin 1000S can receive connections from remote emergency shut-off buttons, gas detectors and a CO2 monitor.
  • Page 4: Circuit Board Terminals

    [POWER LNE]. GAS VALVE The 110-240VAC gas solenoid valve should be powered using the terminals on the Merlin 1000S detailed [GAS VALVE LNE]. BMS OUT Terminal connections are available on the circuit board for Building Management systems etc.
  • Page 5: Em Remote

    Merlin 1000S User Guide EM REMOTE This terminal is for remote emergency shut-off buttons and detailed on the circuit board as [EM REMOTE]. This is linked out as a factory setting. Remote emergency shut-off buttons should be volt free and wired to the Merlin 1000S.
  • Page 6: Installation & Operation

    BMS Integration The Merlin 1000S can be integrated with a BMS to make or break a circuit on gas on/gas off, (valve open or valve closed). This will tell the BMS whether or not power is being sent to the solenoid.
  • Page 7: Fire Alarm Integration

    The Fan Switch provides the facility to turn on the fan(s) when the key switch on the Merlin 1000S is ‘ON’ and turns the power off to the fan(s) when the key switch on the Merlin 1000S is in the OFF position. There is a dip-switch located inside the facia of the Merlin 1000S labelled [EM SEL].
  • Page 8: Panel Led Status

     Gas On When the key switch is turned on, the Merlin 1000S will check the installation for gas leaks. If gas proving is successful, the gas valve will open and the ‘Gas On’ LED will illuminate. ON = Gas On OFF = Gas Off ...
  • Page 9: Maintenance

    Merlin 1000S User Guide  Timeout Under normal working conditions this LED is off. This LED will illuminate AMBER when auto-shut down has occurred. OFF = OK ON = auto-shut down  EM Stop If an emergency shut off button (either remote or on the panel) is pressed, the LED will illuminate AMBER and the gas will be turned off.
  • Page 10: 1000S Wiring Spec

    Merlin 1000S User Guide 1000S Wiring Spec 12 13 Detector Pressure Transducer Monitor Gas Valve Stop 1. POWER: Mains Input 110-240VAC Single Phase. 2. GAS VALVE: Gas Solenoid Valve Power Output, 110-240VAC, Max 3A. 3. ELECTRIC CONTACTOR: Disabled on this system.
  • Page 11 Merlin 1000S User Guide Rev: 07 05-19...
  • Page 12: Manufacturer's Warranty

    Merlin 1000S User Guide Manufacturer’s Warranty 3 Year Limited Warranty Warranty coverage: The manufacturer warrants to the original consumer purchaser, that this product will be free of defects in material and workmanship for a period of three (3) years from date of purchase. The manufacturer’s liability hereunder is limited to replacement of the product with repaired product at the discretion of the manufacture.