Continuous Radar Level Sensor (80GHz)
Wiring Connection
The sensor power supply and current signal share the same two-wire shielded cable. The sensor supply voltage should never
exceed 24 VDC. Always provide complete electrical and physical separation between the sensor supply circuit and the
main circuit.
Note :
Remember that the output voltage of the power supply can be lower under nominal load (with a sensor current of 20.5
mA or 22 mA) and/or with the addition of other instruments placed within the circuit. If voltage spikes or surges are expected,
adequate isolation protection must also be provided.
Terminal Connections
The Positive (+) and Negative (-) terminals are for connection to a 24 VDC power supply or to a 4-20 mA loop power source. The
wire to the terminals can be extended up to 1,000 feet using 16-22 gauge shielded instrumentation wire
01
R
R
ProScan
ProScan
®
®
3 Series
3 Series
24VDC
RS485
10.562m
ESC
ESC
OK
OK
Rotate Anti-clockwise to Open Lid and
Clockwise to Close Lid
Do Not Use Tools!
04
Built-in
Level
24VDC
RS485
Remove Cord Grip
Do Not Use Tools!
The sensor should be wired with shielded 2-conductor cable (16 to 22 AWG) to protect from electromagnetic interference. If
using a liquid tight connector, select a cable with an outer diameter that is designed to ensure an effective seal with the
connector [typically between 0.20" to 0.35" (5 to 9 mm)].
Wiring should always be done by a licensed electrician in accordance with federal, state, provincial and local codes.
23-0167 © Icon Process Controls Ltd.
02
Open Lid
05
Enter Cable in Cable Grip
03
Rotate Anti-clockwise to Open Display and
clockwise to close Display.
06
24VDC
Positive (+)
24VDC
Negative (-)
Positive (+) and Negative (-) terminals are for
connection to a 24 VDC power supply
RS485
5
Need help?
Do you have a question about the ICON ProScan 3 Series and is the answer not in the manual?