• Before attempting to use the SVS (Sollatek Voltage Stabiliser) ensure that the total loading of your equipment does not exceed the maximum rating of the SVS. To check the rating of your SVS, refer to the label on the back of the unit.
230V or 110V (±3 or 6% depending on the model) The Sollatek SVS has either a 12 LED panel or a LED display (depending on the model) to accurately indicate the state of the input and the output voltage.
3. TECHNICAL SPECIFICATION 3.1 GENERAL SPECIFICATION - STANDARD MODELS Input/Output Input Operating Range 230 V Models: 150.5 - 286.5 V 115V Models: 75 - 143 V Input Regulating 230 V Models: 171 - 274 V Range* 115 V Models: 86 - 137 V Output Accuracy ±...
3.2 MODEL SPECIFICATION Input Output Output Power User Dimensions Connector Case Type Weight Voltage Current @ Nominal Interface (mm) STANDARD MODEL SVS20-22 230 V 20 A 4600 VA Cable LED Panel Plastic 162 x 132 x 275 15.0 kg (98220060) SVS20-22 230 V 20 A...
5. INSTALLATION • Isolate mains before installing • Ensure the rating of the load doesn’t exceed the capacity of the SVS, if in doubt consult your electrician. • Ensure that it is positioned so that a free fl ow of air allows the unit to cool.
5.2 METAL WALL MOUNTED BOX • Please ensure that you use correctly rated cable (see table below). 3 or 4 core PVC insulated cables current carrying º capacity (amperes) @ 30 C ambient (conductor º operating at 70 (cross section) Amps •...
SVS1413 – Direct / Socket Connection Internal Connections • Remove the top cover by loosening the two screws on either side of the SVS. L out L out • Insert the supply input cable through the cable 220 V 115 V Fuse access hole on the side of the SVS.
6.2 SVS INTERFACE LED Panel Input voltage status LEDs Input voltage good +5%, +10% Input voltage level of deviation from nominal supply -10%,-15% +15%, -25% Input voltage close to the regulating limits Output voltage status LEDs Output voltage supplied at nominal or within unit accuracy +10%,-10% Accuracy of the output voltage from the nominal supply +15%, -20%...
6.3 OPERATING SEQUENCE Input voltage within the regulating Range If the input voltage is within the regulating range, the SVS will compensate any difference in the input voltage by stepping up or stepping down the output voltage to maintain an optimal output supply.
- 230 V Ensure the mains supply and the SVS is switched on The thermal fuse inside the SVS Contact Sollatek for return has blown. The unit appears to be function- The Load is not plugged in. Ensure the load is plugged in / ing normally but the load is not wired correctly.
The service life of the SVS should be in excess of twenty years if operated within specifi cation. 9. GUARANTEE Sollatek (UK) Ltd guarantee that if within 2 years of purchase this appliance fails due to faulty workmanship or materials we will repair or replace it free of charge provided that: •...