System Set Up; Dip Switch Functions - Mitsubishi Electric ecodan EHST20D-VM2C2 Installation Manual

Table of Contents

Advertisement

5

System Set Up

5.1 DIP Switch Functions

Located on the FTC printed circuit board are 5 sets of small white switches
known as DIP switches. The DIP switch number is printed on the circuit board
next to the relevant switches. The word ON is printed on the circuit board and on
the DIP switch block itself. To move the switch you will need to use a pin or the
corner of a thin metal ruler or similar.
DIP switch settings are listed below in Table 5.1.1.
Only an authorised installer can change DIP switch setting under one's own re-
sponsibility according to the installation condition.
Make sure to turn off both indoor unit and outdoor unit power supplies before
changing the switch settings.
DIP switch
Function
SW1 SW1-1 Boiler
SW1-2 Heat pump maximum outlet water temperature
SW1-3 DHW tank
SW1-4 Immersion heater
SW1-5 Booster heater
SW1-6 Booster heater function
SW1-7 Outdoor unit type
SW1-8 Wireless remote controller
SW2 SW2-1 Room thermostat1 input (IN1) logic change
SW2-2 Flow switch1 input (IN2) logic change
SW2-3 Booster heater capacity restriction
SW2-4 Cooling mode function
Automatic switch to backup heat source operation
SW2-5
(When outdoor unit stops by error)
SW2-6 Mixing tank
SW2-7 2-zone temperature control
SW2-8 Flow sensor
SW3 SW3-1 Room thermostat 2 input (IN6) logic change
SW3-2 Flow switch 2 input (IN3) logic change
SW3-3 Flow switch 3 input (IN7) logic change
SW3-4 Electric energy meter
SW3-5 Heating mode function *3
SW3-6 2-zone valve ON/OFF control
SW3-7 Heat exchanger for DHW
SW3-8 Heat meter
SW4 SW4-1
SW4-2
SW4-3
SW4-4 Indoor unit only operation (during installation work) *4
SW4-5 Emergency mode (Heater only operation)
SW4-6 Emergency mode (Boiler operation)
SW5 SW5-1
SW5-2 Advanced auto adaptation
SW5-3
SW5-4
SW5-5
SW5-6
SW5-7
SW5-8
Note:
*1. When the cylinder unit is connected with a SUHZ-SW outdoor unit of which maximum outlet water temperature is 55ºC, DIP SW1-2 must be changed
to OFF.
*2. External output (OUT11) will be available. For safety reasons, this function is not available for certain errors. (In that case, system operation must
be stopped and only the water circulation pump keeps running.)
*3. This switch functions only when the cylinder unit is connected with a PUHZ-FRP outdoor unit. When another type of outdoor unit is connected, the
heating mode function is active regardless of the fact that this switch is ON or OFF.
*4. Space heating and DHW can be operated only in indoor unit, like an electric boiler. (Refer to "5.5 Indoor unit only operation". )
*5. If emergency mode is no longer required, return the switch to OFF position.
*6. Active only when SW3-6 is set to OFF.
17
WITHOUT Boiler
55ºC
WITHOUT DHW tank
WITHOUT Immersion heater
WITHOUT Booster heater
For heating only
Split type
WITHOUT Wireless remote controller WITH Wireless remote controller
Zone1 operation stop at thermostat short Zone1 operation stop at thermostat open
Failure detection at short
Inactive
Inactive
Inactive
WITHOUT Mixing tank
Inactive
WITHOUT Flow sensor
Zone2 operation stop at thermostat short Zone2 operation stop at thermostat open
Failure detection at short
Failure detection at short
WITHOUT Electric energy meter
Inactive
Inactive
Coil in tank
WITHOUT Heat meter
Inactive
Normal
Normal
Inactive
EHST20D-VM2C2
ERST20D-VM2C2
EHPT20X-VM2C2
OFF
WITH Boiler
60ºC
WITH DHW tank
WITH Immersion heater
WITH Booster heater
For heating and DHW
Packaged type
Failure detection at open
Active
Active
Active *2
WITH Mixing tank
Active *6
WITH Flow sensor
Failure detection at open
Failure detection at open
WITH Electric energy meter
Active
Active
External plate HEX
WITH Heat meter
Active
Emergency mode (Heater only operation) OFF *5
Emergency mode (Boiler operation)
Active
Capacity code
SW5-3 SW5-4 SW5-5 SW5-6 SW5-7
ON
OFF
OFF
ON
OFF
OFF
OFF
OFF
<Table 5.1.1>
<Figure 5.1.1>
Default settings:
ON
Indoor unit model
OFF
ON *1
ON
OFF
ON
ON
OFF: E*ST20D-VM2C2
ON: EHPT20X-VM2C2
OFF
OFF
OFF
OFF: ERST20D-VM2C2
ON: EH*T20*-VM2C2
OFF: EH*T20*-VM2C2
ON: ERST20D-VM2C2
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF *5
OFF
ON
OFF
OFF
OFF
SW5
SW4
SW3
SW2
SW1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ecodan erst20d-vm2c2Ecodan ehpt20x-vm2c2

Table of Contents