Installation Manual for
LONGi Solar PV Modules
V18

Advertisement

Table of Contents
loading

Summary of Contents for LONGI LR5-54HPH M Series

  • Page 1 Installation Manual for LONGi Solar PV Modules...
  • Page 2 • This manual elaborates on installation and safety use information for PV power gener- ating modules (hereinafter referred to as module) of LONGi Solar Technology Co., Ltd. (hereinafter referred to as LONGi). Please abide by all safety precautions in this guide and local regulations.
  • Page 3: Table Of Contents

    Contents 1 / Introduction 2 / Laws and Regulation 3 / General Information 3.1 Modules Identification 3.2 Junction box style and wiring method 3.3 Regular Safety 3.4 Electrical Performance Safety 3.5 Operation Safety 3.6 Fire Safety 4 / Installation Conditions 4.1 Installation Site and Working Environment 4.2 Selection of Tilt Angles 5 / Mechanical Installation...
  • Page 4: Introduction

    LONGi is liable for the losses or expenses incurred only when the module failed above tests. LONGi will not take any responsibility if patent rights or the third party rights are infringed by use of modules. LONGi reserves the rights for modifying product manual or installation manual without advanced notice.
  • Page 5: General Information

    General Information 3.1 Modules identification Three labels on the module contain the information below: 1. Nameplate: product type, rated power, rated current, rated voltage, open circuit voltage, short circuit current under testing conditions, certification indicator, maximum system voltage, etc. 2. Current classification label: Rated working current.(H indicates High, M indicates Medium, L indicates Low). 3.
  • Page 6 Bifacial Modules (With Frame) Frame Front Glass EVA/POE Solar Cell Back Glass Sealant Junction Box Name Plate Mounting Holes 10 Grounding Holes 11 Drain Holes 12 Bar Code Figure 2 Typical Modules Mechanical Drawing (Please refer to section 3.2 for the location of the junction box. The specific version is subject to the corresponding specification.)...
  • Page 7: Junction Box Style And Wiring Method

    3.2 Junction box style and wiring method Junction Box Location Recommended Wiring Method Portrait Installation: Standard Cable length Note: The extra extended cable is required for connection at the turn-back corner of wiring as shown below. Landscape Installation:54/60 type PV module cable length ≥1.2m, 72 type PV module cable length ≥1.4m, 78 type PV module cable length ≥1.5m.
  • Page 8: Electrical Performance Safety

    The application level of LONGi Solar module is Class Ⅱ, which can be used in systems operating at > 50 V DC or >240 W, where general contact access is anticipated; When the modules are for rooftop application, it is necessary to take the overall fire rating of the finished structure as well as operation and maintenance into account.
  • Page 9: Operation Safety

    Please refer to local laws and regulations before installing modules and abide by requirements on building fire protection. According to the corresponding certification standards, the fire rating of LONGi Mono-facial modules is UL Type 1 or 2 or IEC Class C, the fire rating of LONGi bifacial modules is UL Type 29 or IEC Class C.
  • Page 10: Installation Conditions

    Do not install modules at places that are possible to be flooded. • LONGi suggests that modules be installed in the working environment with the temperature of -40℃ to 40℃ of which is the monthly average highest and lowest temperature of the installation sites. The extreme working environment temperature for modules is -40℃...
  • Page 11: Selection Of Tilt Angles

    If the modules output power meets the acquired load under the period of the worst irradiation in the year, the modules should be able to meet the load of the whole year. If the LONGi modules are used in grid-con-...
  • Page 12: Mechanical Installation

    Module and bracket system connection can be realized by mounting holes, clamps or embedded systems. Installation shall follow the demonstration and suggestions below. If installation mode is different, please consult LONGi customer service personnel and obtain approval. Otherwise, modules may be damaged and limited warranty will be invalid. (* Note: regarding to Anti-Soiling modules only, short edge design has applied on prevention of dust from accumulating on modules, therefore , do not install at the short edge.
  • Page 13: Bolts Mounting

    5.2.1 Bolts Mounting The LONGi’s module has mounting holes matching M6 and M8 bolts. See Figure 4 for installation details and corre- sponding hole positions. Mounting Diagram Applicable for modules 790mm (790 hole) 400mm (400 hole) Use M6 bolts LR5-72HPH/HTH/HBD/HGD/HTHF-xxxM*...
  • Page 14: Clamp Mounting

    For framed PV module, it is recommended that the length of the clamp be at least 50mm, the clamp must maintain an overlap of 10-12 mm with the frame of the module (For clamp installation with an overlap of less than 10mm, LONGi technicians need to be consulted for assessment).
  • Page 15: Installation And Mechanical Load Of Mono-Facial Module

    5.3 Installation and Mechanical Load of Mono-facial Module Mono-facial modules can be mounted by bolts or clamps. The mounting method and maximum test load are shown as follow (The unit of distance and length in the table below is millimeter (mm), and the unit of pressure is Pascal (Pa)). Outer four-hole bolts mounting Inner four-hole bolts mounting Mounting rails cross the long frame.
  • Page 16 Short RailV2.4 + Reinforcement LR5-72HPH-xxxM NX Horizon 4×bobtails (M6 head O.D. 16.8 mm) ±1800 LR5-72HTH-xxxM (1P) (400mm holes position) The above data is based on the static load requirements of IEC61215 standard (Tested by LONGi or third party certification institution).
  • Page 17 5.4 Installation and Mechanical Load of Bifacial module Bifacial modules can be mounted by bolts or clamps. The mounting method and maximum test load are shown as follow. (The unit of distance and length in the table below is millimeter (mm), and the unit of pressure is Pascal (Pa)). Outer four-hole bolts mounting Outer four-hole bolts mounting Mounting rails parallel the long frame.
  • Page 18 ﹢ 3600, -2400 LONGi bifacial modules can be matched with the mainstream bracket systems in the industry. The matching test load is as follows (for other bracket systems matching information which are not specified or included in the table below, please...
  • Page 19 Module Type Compatible Support Brackets Mounting Hardware Test Load (Pa) Short Rail V2.4 LR5-66HBD-xxxM NEXTracker NX Horizon(1P) 4×bobtails (M6 head O.D. 16.8 mm) ±2400 (400mm holes position) Short RailV2.4 NEXTracker NX Horizon(1P) 4×bobtails (M6 head O.D. 16.8 mm) ±2100 (400mm holes position) Hi-rise 300mm Clamp ①...
  • Page 20 Compatible Support Brackets Mounting Hardware Test Load (Pa) M8 Bolt+ double hole washer +3600, -2400 LR5-72HBD-xxxM* 1300+1400mmhole position ① The above data is based on the static load requirements of IEC61215 standard (Tested by LONGi or third party certification institution).
  • Page 21: Electrical Installation

    DC electric parts. (LONGi modules maximum system voltage is DC1000V/DC1500V---ac- tually system voltage is designed based on the selected module and inverter model.) The correction value of VOC can be calculated by the following formula.
  • Page 22: Connector

    6.4 Bypass diode LONGi solar module junction box contains bypass diode which is in parallel connection with the cell string. If hot spot occurred, the diode will come into operation to stop the main current from flowing through the hot spot cells in order to prevent module over-heated and performance loss.
  • Page 23: Grounding

    The copper core wire used for the grounding clamp is recommended to be 12 AWG. And copper wires cannot be pressed during installation in case of damaging. The following is one of the recommended grounding methods of LONGi modules: ◆...
  • Page 24: Operation And Maintenance

    Mounting holes on modules that are not occupied can be used for installing grounding devices. The third party grounding device can be used for grounding of LONGi modules but such grounding method shall be proved to be reliable. Grounding device shall be operated in line with stipulations of the manufacturer.
  • Page 25: Module Appearance Inspection

    Do not use acid and alkaline detergents to clean modules. Do not use tool with rough surface to clean in any case. In order to avoid potential risk of electrical shock or burn, LONGi suggests cleaning the modules during early morning or evening with low irradiance and low modules temperature especially for the hot regions.
  • Page 26 LONGi Solar Technology Co, Ltd. No.8369 Shangyuan Road, Xi’an Economic & Technological Development Zone www.longi.com...