2.
Access to the Graphic User Interface via Computer
There are two ways to gain access to the internal Web Server where further setup and configuration is available.
2.1
RJ45 Ethernet Port:
a.
Connect the Vertical Series+ smart PDU to a standard Ethernet network.
b.
Plug the device into an AC power source. By default, the device is set to DHCP and will pull an IP
address once it is connected to an AC power source, assuming that your network is set to DHCP. If your
network is set for a Static IP address, access the unit via the USB-OTG Port, then go into the Network
setting to change over to Static IP addressing.
c.
To find the IP address of the device, download the free SurgeX IP address discovery tool at
www.surgex.com. Alternatively, use a third-party IP address discovery tool or look at the IP table built
into the network's router.
d.
Using any web browser, type in the unit's IP address to access the login page:
e.
The default login credentials are:
Username: admin
Password: Adm1nXXXXXX
XXXXXX are the last six (6) characters of the unit's MAC address. Change your password after logging in for the
first time to minimize security issues.
2.2
USB-OTG Port:
a.
Connect the Vertical Series+ smart PDU to your computer using a USB-A to Micro-USB cable.
b.
Plug the device into an AC power source.
c.
Using any web browser, type in the default IP address https://169.254.10.100 to access the login page: