Thermostat/Subbase Combinations
The T874/Q674 Thermostat/Subbase combinations provide 24 to 30 Vac control for heat pump systems. See Table 1.
Thermostat/
a
Subbase
Model
Heating
T874N/Q674C
T874N/Q674F
T874R/Q674L
a
Q674 Subbase provides the wiring terminals, system switch and fan switch for system operation.
b
Provides manual changeover with the subbase system switch in COOL position.
On a two-heat thermostat, the two stages of heat make
sequentially as the temperature drops. Make refers to the
mercury switch initiating a call for heat or cool.
There are about 2° F [1° C] between stages so that the
second stage makes only when the first stage cannot handle
the load. This is the interstage differential.
One or two LEDs (light emitting diodes) are included on
your subbase. Refer to the list below for specific meaning.
The CHECK LED lights when something needs to be
checked or done to maintain efficient operation of the system.
See your heating system instructions for the specific mean-
ing.
The EM. HT. LED lights when the system switch is placed
in the EM. HT. position. Emergency heat is operating; in
most systems, the compressor has failed and the heat pump
is not operating.
The AUX. HT. LED lights when the auxiliary heat stage
is operating. The weather is cold enough that the first stage
cannot handle the load alone.
LEDs are not field replaceable or addable.
M3375
This control contains mercury in a sealed tube. Do not
place control in the trash at the end of its useful life.
If this control is replacing a control that contains mercury in
a sealed tube, do not place your old control in the trash.
Contact your local waste management authority for in-
structions regarding recycling and the proper disposal of this
control, or of an old control containing mercury in a sealed
tube.
If you have questions, call Honeywell at 1-800-468-1502.
Installation Instructions for the Trained Service Technician.
TABLE 1—T874/Q674 THERMOSTAT/SUBBASE COMBINATIONS.
Number
of Stages
Cooling
Heating
2
1
2
1
2
1
Operation
Recycling Notice
S. M. • Rev. 5-93 •
Changeover
Stage
Cooling
1
1
OFF-EM. HT.-
HEAT-AUTO-COOL
b
2
EM. HT.-HEAT-
WHEN INSTALLING THIS PRODUCT...
1. Read these instructions carefully. Failure to follow
them could cause a hazardous condition.
2. Check the ratings given in the instructions and on the
product to make sure the product is suitable for your applica-
tion.
3. Installer must be a trained, experienced service tech-
nician.
4. After installation is complete, check out product opera-
tion as provided in these instructions.
CAUTION
1. Disconnect power supply to prevent electrical
2. To prevent interference with the thermostat link-
3. Do not overtighten thermostat captive mounting
4. Do not short across coil terminals on the relay.
IMPORTANT: Thermostats are calibrated at the factory
using subbases mounted at true level. An inaccurately
leveled subbase will cause thermostat control devia-
tion.
• ©Honeywell Inc. 1993 • Form Number 60-1147—4
M3375
T874/Q674
Type of Switching
System
Fan
OFF-AUTO
AUTO-ON
AUTO-ON
AUTO-ON
OFF-COOL
shock and equipment damage.
age, keep wire length to a minimum and run
wires as close as possible to the subbase. Push
excess wire back into the hole and plug hole to
prevent drafts from affecting thermostat opera-
tion.
screws because damage to subbase threads may
result.
This may burn out the thermostat heat
anticipator.
Application
See Fig.
5
6
7
Installation

Advertisement

loading

Summary of Contents for Honeywell Q674

  • Page 1 Resideo. It is no T874/Q674 longer manufactured Thermostat/Subbase Combinations Installation Instructions for the Trained Service Technician. Application The T874/Q674 Thermostat/Subbase combinations provide 24 to 30 Vac control for heat pump systems. See Table 1. TABLE 1—T874/Q674 THERMOSTAT/SUBBASE COMBINATIONS. Thermostat/ Number Changeover Subbase...
  • Page 2: Mounting The Subbase

    LOCATION Install the thermostat about 5 ft [1.5 m] above the floor in Fig. 1—Installation of Q674 Subbase on outlet box. an area with good air circulation at average temperature. VERTICAL Do not install the thermostat where it can be affected by: OUTLET —drafts, or dead spots behind doors and in corners.
  • Page 3 Fig. 4—Wiring connections. 3. If LED indication (EM.HT., CHECK, etc.) is to be used FOR STRAIGHT with the Q674 Subbase, install the preprinted insert under the FOR WRAPAROUND– INSERTION– thermostat set point scale (Fig. 8). To install, push both STRIP 7/16 in.
  • Page 4 Fig. 6—Internal schematic and typical wiring diagram for T874N and Q674F. OUTDOOR DEFROST THERMOSTAT REVERSING RELAY VALVE HEAT ANTICIPATOR EM.HT. RELAY RELAY 2 CONTACT EM.HT. RELAY HEAT CONTACT RELAY 3 FALL FAN SWITCH FAN RELAY AUTO ANTICIPATOR FALL HEAT RELAY 1 SYSTEM SWITCH EM.
  • Page 5 Fig. 7—Internal schematic and typical wiring diagram for T874R and Q674L. EM.HT. RELAY CONTACT EM.HT. RELAY HEAT CONTACT CONTACTOR 3 H1/C1 ANTICIPATOR OUTDOOR HEAT THERMOSTAT CONTACTOR 2 DEFROST RELAY HEAT HIGH LIMIT RELAY 1 SWITCH DEFROST REVERSING RELAY VALVE FALL FAN SWITCH OPTIONAL COMP FAILURE DEVICE...
  • Page 6: Temperature Setting

    TEMPERATURE SETTING Fig. 9—Mounting thermostat on subbase. Fig. 11—Location of external components (T874N THERMOSTAT shown). MOUNTING SLOTS (2) HEATING OPTIONAL LED COOLING SET POINT ENUNCIATION SET POINT THERMOSTAT LEVER LEVER MOUNTING POST (2) HEAT COOL XXXX XXXX XXXX XXXX 50 60 50 60 50 60 70 80 SUBBASE...
  • Page 7 HEATING bottom of cover until it clears the mounting slots. Move the system switch on the Q674 to HEAT or AUTO 2. Set the thermostat cover on a table near an accurate (if used) and the fan switch to AUTO. Move the heating set thermometer.
  • Page 8 Automation and Control Solutions Honeywell International Inc. Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55422 Scarborough, Ontario M1V 4Z9 60-1147 –4 S.M. Rev. 5-93 www.honeywell.com/yourhome 60-1147-4...

This manual is also suitable for:

T874T874nQ674cQ674fT874rQ674l