  • Page 1 SKH4 High-Pressure Atomizer BACnet Communication Module User Guide SKH4-BACnet Guide-231108 (V0.16)
  • Page 2: Table Of Contents

    SKH4 High-Pressure Atomizer BACnet Communication Module User Guide Contents Introduction ................................ 1 Pre-requisites ..............................1 Advantages of BACnet ........................... 1 BACnet Properties Configuration ........................2 Configuration Options ............................3 Quick Setup ..............................3 Manual Setup ..............................3 IP Port ................................4 Network Reset ..............................
  • Page 3: Introduction

    BACnet Communication Module User Guide Introduction The SKH4 High-Pressure Atomizer BACnet Communication Module User Guide provides information about using the humidifiers with BACnet communications feature. The BACnet communication protocol for building automation and control networks enables communication between client devices within a network. The humidifier provides a BACnet network interface between BACnet client devices and Neptronic humidifiers.
  • Page 4: Bacnet Properties Configuration

    Device Object.Max_Master. For more information, refer to the MAC Address and Max_Master section. • Device Name of the Configure the name of the device through the WriteProperty service to Object.Object_Name device Device Object.Object_Name. For example, SKH4. www.neptronic.com Page | 2...
  • Page 5: Configuration Options

    Configuration through the Write Property service. See Table 1 - BACnet Properties Configuration. Repeat the steps for each humidifier. Manual Setup Configure the humidifier for BACnet communication using the SKH4 controller, by using the following steps: Press the Enter key. Enter the Integration menu password: 5544.
  • Page 6: Ip Port

    SKH4 High-Pressure Atomizer BACnet Communication Module User Guide Example 3 • MAC=0, Max_Master=1 • MAC=2, Max_Master=2 This is an incorrect configuration. The MAC=0 will never find MAC=2 because it will never poll for the master MAC address=2. Example 4 •...
  • Page 7: Device Object Properties

    • The device instance must be unique system-wide • The def ault value f or the device instance= 153001 (Vendor_Identif ier*1000 + MAC) Object_Name SKH4, programmable up to 32 Bytes Description Programmable up to 32 Bytes (def ault: SKH4 Controller) Object_Type Device System_Status Operational...
  • Page 8: Object Types Supported

    SKH4 High-Pressure Atomizer BACnet Communication Module User Guide Property Value Writable Property_List List of properties that exist within the object. Object Types Supported The following table lists all the BACnet properties supported for each object type. Most of the properties are locked. The exception is Present_Value, which represents the dynamic operating values of the device, and the Status_Flag, Event_State, and Reliability properties, which reflect the availability of the Present_Value.
  • Page 9: Out_Of_Service Property

    Out_of_Service Property Neptronic humidifiers offer the use of the Out_of_Service writable property. When the value of this property is set to True, it disconnects the object from the physical input, enabling you to input other values. This is useful for special applications or while troubleshooting.
  • Page 10: Object Table Information

    Object Table Information The SKH4 uses the following BACnet object tables, categorized on the basis of their ID. The type is the BACnet Object type, the instance is the BACnet Object. Together, the type and instance form the BACnet Object_Identifier for an object according to the following C-language algorithm: •...
  • Page 11: Analog Output (Ao)

    SKH4 High-Pressure Atomizer BACnet Communication Module User Guide Analog Output (AO) Table 5 - Object Table Information: Analog Output (AO) Name List Description Notes Out_of _Service AO.1 Power Output Feedback Signal Integrator Value of the power output f eedback signal.
  • Page 12 SKH4 High-Pressure Atomizer BACnet Communication Module User Guide Name List Description Notes Out_of _Service AV.51 Room RH Max Integrator Maximum value of the room humidity analog input. 0% to 100%, Resolution 1% Present_Value COV_Increment Out_of _Service AV.52 Room RH Bias Integrator Bias value of the room humidity analog input.
  • Page 13 SKH4 High-Pressure Atomizer BACnet Communication Module User Guide Name List Description Notes Out_of _Service AV.86 Power Output Feedback Min Integrator Minimum value of the power output f eedback signal. 0V to 10V, Resolution: 0.001V Present_Value COV_Increment Out_of _Service AV.87 Power Output Feedback Max Integrator Maximum value of the power output f eedback signal.
  • Page 14 SKH4 High-Pressure Atomizer BACnet Communication Module User Guide Name List Description Notes Present_Value RH Supply High Limit Network Out_of _Service AV.122 Integrator Value of the supply high limit reading received f rom the network. 0% RH to 100% RH, Resolution 1% RH...
  • Page 15 SKH4 High-Pressure Atomizer BACnet Communication Module User Guide Name List Description Notes Present_Value Out_of _Service -40°F to 302°F or -40°C to 150°C AV.152 Room Temperature Max Integrator Maximum value of the room temperature signal. COV_Increment Resolution 0.018.°F or 0.01°C Relinquish_Def ault...
  • Page 16 SKH4 High-Pressure Atomizer BACnet Communication Module User Guide Name List Description Notes Out_of _Service -40°F to 500°F or -40°C to 260°C AV.170 HRL Temperature Integrator Displays the room temperature value measured by the HRL24 controller. COV_Increment Resolution 0.18.°F or 0.1°C...
  • Page 17 SKH4 High-Pressure Atomizer BACnet Communication Module User Guide Name List Description Notes Present_Value Temp Supply High Limit Derivative Out_of _Service AV.182 Integrator Conf iguration value of the supply high limit temperature derivative time. 0 second to 60 seconds, Resolution: 0.1 second...
  • Page 18 SKH4 High-Pressure Atomizer BACnet Communication Module User Guide Name List Description Notes Present_Value Out_of _Service AV.234 Control Timer Integrator Conf iguration value of the control timer. 0 second to 120 seconds, Resolution: 1 second COV_Increment Relinquish_Def ault Out_of _Service AV.235...
  • Page 19 SKH4 High-Pressure Atomizer BACnet Communication Module User Guide Name List Description Notes Present_Value Out_of _Service -40°F to 302°F or -40°C to 150°C AV.251 Zone D Temperature Integrator Conf iguration value of the temperature f or Zone D. COV_Increment Resolution 0.018.°F or 0.01°C...
  • Page 20 SKH4 High-Pressure Atomizer BACnet Communication Module User Guide Name List Description Notes Present_Value Out_of _Service AV.265 Stage 2 Capacity Integrator Conf iguration value of the capacity f or stage 2. 0l/h to 3000l/h, Resolution 1l/h COV_Increment Relinquish_Def ault Present_Value Out_of _Service AV.266...
  • Page 21 SKH4 High-Pressure Atomizer BACnet Communication Module User Guide Name List Description Notes Out_of _Service AV.279 Stage 1 Drain Time Integrator Displays the value of the drain time f or stage 1. COV_Increment 0 second to 9999 seconds, Resolution: 1 second...
  • Page 22 SKH4 High-Pressure Atomizer BACnet Communication Module User Guide Name List Description Notes Out_of _Service 0 second to 21474836.47 seconds, Resolution: 0.01 AV.313 Stage 1 Run Time Integrator Displays the value of the run time f or stage 1. COV_Increment second...
  • Page 23 SKH4 High-Pressure Atomizer BACnet Communication Module User Guide Name List Description Notes Present_Value Out_of _Service AV.382 Stage 1 Max On Time Integrator Set the maximum on time f or stage 1. 0 second to 1200 seconds, Resolution: 1 second COV_Increment...
  • Page 24 SKH4 High-Pressure Atomizer BACnet Communication Module User Guide Name List Description Notes Present_Value Out_of _Service AV.392 Stage 5 Pause Time Integrator Set the pause time f or stage 5. 0 second to 1200 seconds, Resolution: 1 second COV_Increment Relinquish_Def ault...
  • Page 25 SKH4 High-Pressure Atomizer BACnet Communication Module User Guide Name List Description Notes Out_of _Service AV.403 Drain 4 Cycle Count Integrator Displays the value of the drain cycle count f or stage 4. COV_Increment 0 to 999999999, Resolution: 1 Relinquish_Def ault Out_of _Service AV.404...
  • Page 26 SKH4 High-Pressure Atomizer BACnet Communication Module User Guide Name List Description Notes Present_Value Out_of _Service AV.416 Zone C MAC Integrator Set the value of the MAC address f or Zone C. 0 to 127, Resolution: 1 COV_Increment Relinquish_Def ault Present_Value Out_of _Service AV.417...
  • Page 27: Binary Input (Bi)

    SKH4 High-Pressure Atomizer BACnet Communication Module User Guide Binary Input (BI) Table 7 - Object Table Information: Binary Input (BI) Name List Description Notes Out_of _Service 0 = Closed Integrator Displays the status of the airf low switch. If the switch is Open, it indicates that the BI.1...
  • Page 28: Binary Output (Bo)

    SKH4 High-Pressure Atomizer BACnet Communication Module User Guide Binary Output (BO) Table 8 - Object Table Information: Binary Output (BO) Name List Description Notes Present_Value Out_of _Service Polarity 0 = Of f BO.2 Alarm Warning Relay Integrator Status value f or the alarm warning relay.
  • Page 29 SKH4 High-Pressure Atomizer BACnet Communication Module User Guide Name List Description Notes Present_Value Out_of _Service Polarity 0 = Of f BO.10 Valve 6 Integrator Status value f or valve 6. Relinquish_Def ault 1 = On Minimum_Of f _Time Minimum_On_Time Present_Value...
  • Page 30 SKH4 High-Pressure Atomizer BACnet Communication Module User Guide Name List Description Notes Present_Value Out_of _Service Polarity 0 = Of f BO.19 Power LED Integrator Status value f or the power LED. Relinquish_Def ault 1 = On Minimum_Of f _Time Minimum_On_Time...
  • Page 31: Binary Value (Bv)

    SKH4 High-Pressure Atomizer BACnet Communication Module User Guide Binary Value (BV) Table 9 - Object Table Information: Binary Value (BV) Name List Description Notes Present_Value Conf iguration value that enables or disables the alarm buzzer sound when there Out_of _Service 0 = Normal BV.3...
  • Page 32 SKH4 High-Pressure Atomizer BACnet Communication Module User Guide Name List Description Notes Present_Value Out_of _Service 0 = No BV.70 Stage 1 Diagnostic Enable Integrator Select the status of the diagnostic enable f or stage 1. Minimum_Of f _Time 1 = Yes...
  • Page 33: Character String Value (Cv)

    SKH4 High-Pressure Atomizer BACnet Communication Module User Guide Character String Value (CV) Table 10 - Object Table Information: Character String Value (CV) Name List Description Notes CV.10 HMI Overwrite Integrator Overwrite the value displayed on the local display menu. Present_Value CV.22...
  • Page 34: Multi State Value (Msv)

    SKH4 High-Pressure Atomizer BACnet Communication Module User Guide Multi State Value (MSV) Table 11 - Object Table Information: Multi State Value (MSV) Name List Description Notes 1 = None 2 = Emergency 3 = Alert 4 = Critical Present_Value MSV.5 System Log Verbose Level Integrator Conf iguration value to select the type of inf ormation to be stored on the log f ile.
  • Page 35 SKH4 High-Pressure Atomizer BACnet Communication Module User Guide Name List Description Notes 1 = Disabled 2 = ExternAnalog 3 = ExternNetwork Conf iguration value to select a preconf igured control mode prof ile f or the 4 = InternHumAnalog MSV.29...
  • Page 36 SKH4 High-Pressure Atomizer BACnet Communication Module User Guide Name List Description Notes 1 = None Temp Supply High Limit Present_Value MSV.71 Integrator Conf iguration value to select the temperature supply high limit reading source. 2 = SupplyHLTemp Reading Source Out_of _Service...
  • Page 37 SKH4 High-Pressure Atomizer BACnet Communication Module User Guide Name List Description Notes 1 = Of f 2 = Normal Present_Value MSV.99 Zone C Control Integrator Select the control mode f or zone C. 3 = Airf low Out_of _Service 4 = SupplyHighLimit...
  • Page 38 SKH4 High-Pressure Atomizer BACnet Communication Module User Guide Name List Description Notes 1 = Drain7 2 = Drain8 Present_Value 3 = Drain9 MSV.108 Stage1 Drain Integrator Select the stage 1 drain. 4 = Drain10 Out_of _Service 5 = Drain11 6 = Drain12...
  • Page 39 SKH4 High-Pressure Atomizer BACnet Communication Module User Guide Name List Description Notes 1 = ZoneA 2 = ZoneB Present_Value 3 = ZoneC MSV.115 Stage 5 Zone Integrator Select the stage 5 zone. 4 = ZoneD Out_of _Service 5 = ZoneE...
  • Page 40: Other

    SKH4 High-Pressure Atomizer BACnet Communication Module User Guide Other Table 12 - Object Table Information: Other Name List Description Notes Program_Change Program Change, only LOAD (1) and RESTART (4) PGM.1 NSDF Core Program Advanced NSDF Core Program. Out_of _Service are supported.
  • Page 41 SKH4 High-Pressure Atomizer BACnet Communication Module User Guide Name List Description Notes FIL.16 System Log File Integrator System Log f ile. File_Size File size is accepted f or 0 value only. FIL.19 UpdatePackageFile Advanced Update Package f ile. File_Size File size is accepted f or 0 value only.
  • Page 42 Notes...