Omniaire 2500 Series Operation And Maintenance Manual

Hepa air filtration machine

Advertisement

Quick Links

2500 Series
HEPA Air Filtration Machine
Operation and Maintenance Manual
1

Advertisement

Table of Contents
loading

Summary of Contents for Omniaire 2500 Series

  • Page 1 2500 Series HEPA Air Filtration Machine Operation and Maintenance Manual...
  • Page 2: Safety Warning Instructions

    WARNING Do not use with combustible or explosive material. Do not expose to water or rain. Connect only to grounded outlet with GFCI device. Disconnect power for cleaning and servicing. This equipment to be operated only by trained personnel. CONFORMS TO UL STD 507: 2017 Ed.10+R:27May2020 CERTIFIED TO CAN/CSA STD C22.2 NO.
  • Page 3: Receiving Instructions

    The OmniAire 2500 series is family of construction grade negative air machines, featuring three models with progressive features. These machines contain a powerful blower and a 24”x24” HEPA, either 6” or 12” deep. These machines, along with their many accessories can be used to remove airborne particulates and biocontaminants in many applications, including abatement and construction.
  • Page 4: Start The Machine

    Start the machine The OA2500 PRIME and OA2500 PLUS models have a two-speed switch; place the switch in the HIGH or LOW position to turn the machine on. The OA2500 PRO model has a dial to turn on the machine and adjust the speed as needed.
  • Page 5: Hepa Filter

    HEPA clips for the 12” deep HEPA to hold the prefilter in place, as illustrated below: HEPA Filter Your OmniAire Negative Air Machine comes equipped with a pressure sensor that will notify you when your HEPA filter is nearing its full capacity. When this occurs a “change filter” indicator light on the front panel turns on (and will stay on).
  • Page 6 AS HAZMAT AND PROCESS IT ACCORDING TO YOUR ESTABLISHED HAZMAT PROCEDURES. To replace the HEPA filter ensure that the gasket on the HEPA filter faces inwards toward the flange, slide the filter in place along the filter guides and re-install the filter tabs and filter tab securing nuts. Tighten the tabs so that the gasket is compressed approximately ½...
  • Page 7 HEPA Model Specifications Likely Pressure Sensor Range OAH2424-10 6” Depth, Standard Capacity, 99.97% Efficiency 550-580 OAH2424-20 12” Depth, Standard Capacity, 99.97% Efficiency 500-550 OAH2424-30 12” Depth, High Capacity, 99.97% Efficiency 480-530 OAH2424-40 12” Depth, Standard Capacity, 99.99% Efficiency 480-530 OAH2424-50 12”...
  • Page 8: Troubleshooting

    Troubleshooting Your OmniAire machine is designed and engineered to provide years of trouble free service. Occasionally problems occur. Here are some helpful tips and solutions. The machine does not start Check that the unit is plugged in and there is 115VAC available. Select either LOW or HIGH speed to turn the machine on (PRIME/PLUS), or turn dial to power on the unit (PRO) Check the circuit breaker and reset if necessary.
  • Page 9 Omni CleanAir LIMITED WARRANTY This warranty policy covers Equipment (Machines and Accessories) sold by Omni CleanAir and applies to the OmniClean, OmniTec, and AgriAir portfolio of brands. Omni CleanAir warrants that our products are free from defects in workmanship and materials under normal use during the warranty period.