Panasonic U-8ME2R8 Installation Instructions Manual page 50

Table of Contents

Advertisement

7-4. Auto Address Setting
Example: Basic Wiring Diagram (1)
• Case of no link wiring
(Inter-unit control wiring is not connected to a multiple system.)
Indoor unit address setting is possible without starting the compressor.
Unit 1 setting (outdoor main unit)
System address
(System 1 setting)
(SW1)
(SW2)
ON
Number
of outdoor
units (3 units
setting)
Outdoor Unit
Remote controller
Case 1
Auto Address Control from Outdoor Unit
1. Regarding the number of outdoor units, set the Dip switch (SW6) for setting the number of outdoor units on Unit 1 control P.C.B to 3
ON
ON
units
and the Unit Number Setting Dip switch (SW5) to unit number 1.
1
2
3
OFF
This unit becomes the outdoor main unit.
2. Set the Unit Number Setting switch (SW5) on unit 2 control P.C. board to unit number 2.
Set the Unit Number Setting switch (SW5) on unit 3 control P.C. board to unit number 3.
3. Check the refrigerant system's Address Setting Rotary switch (SW1) on outdoor main unit control P.C. board to "1" and the Dip switch
(SW2) to "0" (at shipment).
4. Regarding the setting of the number of indoor units connected to the outdoor unit, set the Dip switch (SW4) for setting the number of
indoor units on outdoor main unit control P.C. board connected to the outdoor unit to "1".
If the Rotary switch (SW3) set to "0", 10 units can be prepared for operation.
5. Turn on power to indoor and outdoor units.
6. Short circuit the A.ADD pin (CN30) on outdoor main unit control P.C. board for over 1 second long and open circuit.
Communication for auto address setting begins.
* To cancel, short circuit the A.ADD pin (CN30) again for over 1 second long and then open circuit. The LED that
indicates auto address setting goes out and the process is stopped.
Be sure to perform auto address setting again.
Auto address setting is completed when LEDs 1 and 2 on outdoor main unit control P.C. board go out.
7. Remote control operation is now available.
* When auto address setting is controlled by the remote controller, perform auto address setting by the remote controller after step 5
described above.
No. of indoor units
(10 units setting)
(SW3)
0
ON
(SW4)
ON
ON
1
2
OFF
1
2
3
OFF
(SW6)
Unit
(SW5)
ON
number
ON
ON
setting
2
3
1
OFF
(unit 1)
1
2
3
Set the terminating
resistance plug
socket to SHORT
Unit 1
side. (CN67)
(Main)
Inter-outdoor unit
control wiring
Inter-unit control wiring
1-1
Indoor unit
ON
ON
1
2
OFF
* It is not necessary to control the terminating
resistance plug (3P) (CN67) socket on the
outdoor unit P.C. board.
3P plug is plugged in SHORT side at shipment.
Confirm it is plugged in SHORT side.
Unit 2 setting
(SW5)
Unit
ON
ON
number
ON
setting
1
2
3
OFF
(unit 2)
OFF
Unit 2
(Sub)
Inter-outdoor unit
control wiring
1-2
1-3
Remote control
communication wiring
50
Unit 3 setting
(SW5)
Unit
ON
ON
number
setting
1
2
3
OFF
(unit 3)
Unit 3
(Sub)
1-10
ON
1
2
3
ON
1
2
3
ON
1
2
3
ON
ON
1
2
3
OFF
3P terminating
resistance plug
(SHORT side)
SHORT
OPEN

Advertisement

Table of Contents
loading

Table of Contents