Sentinel
Kinetic 200ZMH(F)
Installation & Commissioning
PLEASE RETAIN THESE INSTRUCTIONS WITH THE PRODUCT.
Model
200ZMH(F)
Copyright © 2009 Vent-Axia Limited. All rights reserved.
Stock Ref. N°
408689

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 200ZMH(F) and is the answer not in the manual?

Questions and answers

Summary of Contents for Sentinel 200ZMH(F)

  • Page 1 Sentinel Kinetic 200ZMH(F) Installation & Commissioning Model Stock Ref. N° 200ZMH(F) 408689 PLEASE RETAIN THESE INSTRUCTIONS WITH THE PRODUCT. Copyright © 2009 Vent-Axia Limited. All rights reserved.
  • Page 2 24. IF THE DUCTWORK OR CONDENSATE PIPE PASSES THROUGH AN UNHEATED LOFT VOID OR SIMILAR LOCATION 8. THESE UNITS MUST BE EARTHED. IT SHOULD BE INSULATED. 9. SENTINEL AIR HANDLING UNITS ARE DESIGNED AND SPECIFIED FOR USE WITH VENT-AXIA CONTROLS, DAMPERS, GRILLES AND ACCESSORIES. Disposal 10.
  • Page 3: Table Of Contents

    UK Building Regulations (Part F) Product Description Declaration of Conformance Sentinel Kinetic 200ZMH(F) ............4 The Sentinel Kinetic conforms to the 2010 Building Technical Data Regulations (Approved Document F - Means of Ventilation) Unit Dimensions ................6 for installed performance of a ducted mechanical extract Overview ..................
  • Page 4: Product Description

    Summer By Pass. The Sentinel Kinetic is fitted with a Summer By Pass (SBP) and will provide energy-free heating and energy-free cooling when the house temperature and ambient temperature allows. Note that the volume of air provided by this ventilation system is a fraction of that required for space heating or space cooling and will not in itself be sufficient to cool a room.
  • Page 5: Technical Data

    Condensate pipe 22 mm diameter Environmental IP Rating IP22 Operating Temperature -10C to +45C Operating Humidity 0% to 95% RH For all other technical details, please see the Product Catalogue or our website at www.ventaxia.com Sentinel Kinetic MVHR Installation & Commissioning...
  • Page 6: Unit Dimensions

    Technical Specification & Installation Unit Dimensions Sentinel Kinetic MVHR Installation & Commissioning...
  • Page 7: Overview

    Take into consideration the position of the electrical services and the condensate drain. Ensure there is adequate access for installation, operation and maintenance. It is recommended that a local disconnection mains and sensor terminal box is installed within 1m of the unit to facilitate future maintenance. Sentinel Kinetic MVHR Installation & Commissioning...
  • Page 8 Leave approximately “a half turn” loose on each of the fixings. This will allow each bracket to be moveable until final fitting of the unit and makes any adjustments easier while installing the unit in position. Sentinel Kinetic MVHR Installation & Commissioning...
  • Page 9 Stage 4: Finally, with the unit secure you can Security fixing now fix the security fixing (as pictured right). Once secured you may proceed with the rest of the installation Sentinel Kinetic MVHR Installation & Commissioning...
  • Page 10: Duct Layout

    Always use a short piece of flexible ducting 100-150mm long, extended to its full length when connecting to ductwork. Securely connect this ducting to the spigots using worm-drive clips or cable ties and duct tape. Insulate any ducting passing through an unheated space to prevent any heat losses and surface condensation. Sentinel Kinetic MVHR Installation & Commissioning...
  • Page 11: Electrical Installation

    3. Connect the cable assembly to the Remote Control terminal block (the terminal block is colour coded to match the individual coloured cables and mount onto a single gang recessed wall box with the 2 screws provided. The wired remote Control will automatically be detected. Yellow Black Green Sentinel Kinetic MVHR Installation & Commissioning...
  • Page 12 Ensure that you use a grommet or gland to protect against potential water ingress. Other means of connecting the unit can be used if they meet the local wiring regulations. SEE NOTES ON PAGE 13 Sentinel Kinetic MVHR Installation & Commissioning...
  • Page 13 One end of the power cable supplied is already connected to the unit. Connect the other end of the cable to the switched fused spur. Use cable clamps and clips to secure the cable, as appropriate. Sentinel Kinetic MVHR Installation & Commissioning...
  • Page 14 LS connection. Alternatively an isolator relay controller, part number 442030, may be used. The live supply to the unit should be fused at 3A. Example wiring diagrams are available via Vent-Axia Technical support, e.g. Drawing Number 448144. Sentinel Kinetic MVHR Installation & Commissioning...
  • Page 15: Powering Up The Unit

    2 seconds for fast scrolling. Press to activate Boost mode. See page 17 for options. Press and hold for 5 seconds to activate Purge mode. (Press and hold for 5 seconds to cancel Purge). Sentinel Kinetic MVHR Installation & Commissioning...
  • Page 16: Start-Up Screens

    Start Up Start-up Screens Sentinel Kinetic Version Screen The Sentinel Kinetic Version screen displays the firmware version number for 3 seconds. No adjustments are possible on this screen. Language Screen The Language screen displays the language used for Language the screens. It is typically displayed for 5 seconds, or English longer if changing the setting.
  • Page 17 N.B Alternative functions are assigned to S/W1, S/W2, S/W3 & SW5 when Control Mode 02 is selected in the start-up screens see Appendix One for further details. Sentinel Kinetic MVHR Installation & Commissioning...
  • Page 18 Return to the normal display by pressing the button or leave to timeout and return automatically after 2 minutes. See Page 4 for a description of this function. Options available are Normal (default), Evening Purge, Night time purge and Off. Sentinel Kinetic MVHR Installation & Commissioning...
  • Page 19 2 minutes. This function will only work when the Summer Mode is set to on. Return to the normal display by pressing the button or leave to timeout and return automatically after 2 minutes Sentinel Kinetic MVHR Installation & Commissioning...
  • Page 20: Commissioning

    The following is attached to the unit and should be used as a check list prior to setting the air flows. Sentinel Kinetic MVHR Installation & Commissioning...
  • Page 21: Wired Remote Control Screens Summary

    Anti-frost 1 air flow mode All Set Anti-frost 2 bypass mode Anti-frost 3 pre-heater and air flow mode Anti-frost 4 pre-heater and bypass mode Set Service No Security PIN? Humidity Sensor Restore Defaults Timeout after 2 minutes Sentinel Kinetic MVHR Installation & Commissioning...
  • Page 22: Commissioning Screens

    Extract airflow speed for the Extract fan in order to 50 % balance out any differences in ductwork or other installation features. Default Boost speed = 50%. The Boost speed cannot be set above the Cooker Hood speed or below Normal speed setting. Sentinel Kinetic MVHR Installation & Commissioning...
  • Page 23 The Low speed cannot be set below 1% or above Normal speed setting. Cooker Hood Supply & Extract Screens Ckr Hood Supply The Cooker Hood Supply & Extract screens are non-functional. Ckr Hood Extract 100% Sentinel Kinetic MVHR Installation & Commissioning...
  • Page 24 Setting finishes when the last off minutes for Sun3 are accepted, at which point the screen will now show All Set or holding the button for 3 seconds. Boost On All Set Sentinel Kinetic MVHR Installation & Commissioning...
  • Page 25 2 seconds to clear service number. Internal Humidity Sensor Screen The Humidity Sensor screen enables you to switch the Humidity Sensor Sensor On and adjust the trigger point between 60% and 70 %. (default setting 70%). Sentinel Kinetic MVHR Installation & Commissioning...
  • Page 26 Table 2: Boost & Normal Limits – Defaults and Adjustment Range Sensor Humidity Temperature Default (%) Range (%) Default (ppm) Range (ppm) Default (°C) Range (°C) Boost limit 25-90 2000 200-2000 10-35 Normal limit 25-90 1000 200-2000 10-35 Sentinel Kinetic MVHR Installation & Commissioning...
  • Page 27 Selectable range: min. = 1, max. = 25, default = 20. Ventwise Input Momentary closure (1 sec) starts or stops boost for set SW4 Momentary time. Selectable range: min. = 15, max. = 30. Default = 25 when Vent-Wise card fitted Sentinel Kinetic MVHR Installation & Commissioning...
  • Page 28 Bypass Mode - While the supply air temperature is below 0°C, the antifrost mode will automatically activate. This mode will open the bypass to prevent frost forming on the heat exchanger. Sentinel Kinetic MVHR Installation & Commissioning...
  • Page 29 (18 months). BMS screen On for BMS (default) or Off for Wired Remote Control, BMS Mode automatically set up by BMS signal or Wired Remote Control when either is plugged into BMS RJ11 socket. Sentinel Kinetic MVHR Installation & Commissioning...
  • Page 30 Available options: No (default) and Yes. The default commissioning settings are present when the unit is switched on and can be restored by setting the Restore Defaults screen to Yes Sentinel Kinetic MVHR Installation & Commissioning...
  • Page 31 Running Time Filter Life Suburban (default) 12 months, or can be set to Urban and Rural Restore Defaults User Screens Set Clock Summer Mode Summer Bypass On Indoor Temp 25 C Outdoor Temp 14 C Sentinel Kinetic MVHR Installation & Commissioning...
  • Page 32: Maintenance

    Maintenance Maintenance Heat recovery units, by their very nature, require regular maintenance. The Sentinel Kinetic 200ZMH(F) have been designed to facilitate access to enable maintenance to be carried out easily. WARNING THE FAN AND ANCILLARY CONTROL EQUIPMENT MUST BE ISOLATED FROM THE POWER SUPPLY DURING MAINTENANCE.
  • Page 33: 12 Monthly Maintenance

    Caution: there may be water in the Condensate Tray, Condensate pipe and Heat recovery cell, possibly up to 1.5 litres, that may spill during this operation. Stage 1: Isolate the mains power supply and undo the securing screws and remove the Cover. Cover Sentinel Kinetic MVHR Installation & Commissioning...
  • Page 34 1.5 litres, that may spill during this operation. Condensate Tray Heat Exchanger Stage 4: Unscrew and remove the two Heat Exchanger fixing Brackets. Heat Exchanger should remain wedged in place Brackets Sentinel Kinetic MVHR Installation & Commissioning...
  • Page 35: Spares

    Filters, 2 per pack 449524 Heat Recovery Cell 449525 Motor assembly 408911 Control PCB 449527 Temperature sensor kit (consists of a T1 & T2 sensor) 449528 Wired remote controller (complete with 15 metre control cable) 443283 Sentinel Kinetic MVHR Installation & Commissioning...
  • Page 36: Troubleshooting

    If you are within the commissioning screens the Antifrost and Room Too Cold Failures modes will not operate allowing the flow rates to be adjusted even in a property which is below 5C. Sentinel Kinetic MVHR Installation & Commissioning...
  • Page 37: Appendix One Control Mode 02 Description

    (see Service/Fault Code Screens on page 36). Mains Live 220-240 V AC, 50 Hz input Mains Neutral 220-240 V AC, 50 Hz input EARTH Mains Earth Earthing connector Switched Live 220-240 V AC, 50 Hz input Sentinel Kinetic MVHR Installation & Commissioning...
  • Page 38: Airflow Mode Selection

    ‘take over’ the boost. Flow will return to normal when that device switches off. If a number of different devices are calling for boost flow, the unit will run at boost until the last one has reverted to normal. Sentinel Kinetic MVHR Installation & Commissioning...
  • Page 39: Appendix Two Options And Accessories

    -15°C at the heat recovery unit. It is set up through the controller on the Sentinel Kinetic, see pages 21 and following. The controller ensures that the heater uses the minimum of electricity by maintaining the incoming air at an average of 0°C.
  • Page 40 Guarantee Applicable only to products installed and used in the United Kingdom. For details of guarantee outside the United Kingdom contact your local supplier. Vent-Axia guarantees its products for two years from date of purchase against faulty material or workmanship. In the event of any part being found to be defective, the product will be repaired, or at the Company’s option replaced, without charge, provided that the product:- ...