Download Print this page

norweco HYDRO-KINETIC 3780L Installation And Operation Manual page 2

Wastewater treatment system with 4 chamber treatment tank

Advertisement

Wastewater enters the pretreatment chamber to precondition the waste before it flows into the anoxic chamber. Once in the
anoxic chamber, facultative anaerobes digest organic matter. Flow then enters the aeration chamber where aerobic bacteria
biologically convert the waste into stable substances and oxidize ammonia into nitrite and nitrate. Following aeration, liquids flow
to the clarification chamber where gravity settles out biologically active material. A recirculation pump in the clarifier transfers
a portion of the wastewater back to the anoxic chamber where nitrogen compounds are converted to harmless nitrogen gas.
From the clarifier, treated liquids pass through the flow equalization devices and into the disposal system. Effluent passes
through the Bio-Film Reactors for final treatment.
The Hydro-Kinetic system is certified to BNQ Standard 3680-600 Class B-IV, D-I, N-I and BNQ Standard 3680-910 Class III,
averaging effluent quality of 3.0 mg/L CBOD, 2.0 mg/L TSS, 67% Nitrogen removal and 2,200 CFU/100 ml fecal coliform.
The Hydro-Kinetic system with Phos-4-Fade filter is certified to BNQ Standard 3680-600 Class B-IV, D-I, N-I, P-II and BNQ
Standard 3680-910 Class IV, averaging effluent quality of 3.0 mg/L CBOD, 2.0 mg/L TSS, 67% Nitrogen removal, 0.14 mg/L
Total Phosphorus and 2,200 CFU/100 ml fecal coliform. The Hydro-Kinetic system with UV disinfection is certified to BNQ
Standard 3680-600 Class B-IV, D-III, N-I and BNQ Standard 3680-910 Class V, averaging effluent quality of 3.0 mg/L CBOD,
2.0 mg/L TSS, 67% Nitrogen removal and 2 CFU/100 ml fecal coliform. The Hydro-Kinetic system with activated alumina filter
and UV disinfection is certified to BNQ Standard 3680-600 Class B-IV, D-III, N-I, P-II and BNQ Standard 3680-910 Class IV
& V, averaging effluent quality of 3.0 mg/L CBOD, 2.0 mg/L TSS, 67% Nitrogen removal, 0.14 mg/L Total Phosphorus and 2
CFU/100 ml fecal coliform.
Before You Start
Installation procedures, equipment and personnel should always comply with applicable safety regulations as well as all federal,
state and local codes. The Hydro-Kinetic system must be installed by an authorized representative of Norweco according to
these instructions to insure safe, reliable and efficient operation. Carefully unpack and inspect the system components.
Make sure you have received all components in good condition. Read all instructions before beginning installation. The
Hydro-Kinetic system components include:
1.
Service Pro Model 801P Control Center
2.
Model A150 Air Pumps (with power wire junction box) (2 required)
3.
Alarm Float (with alarm wire junction box)
4.
Flow Equalization Device (2 required)
5.
Primary Recirculation Assembly
6.
Model SD103 Recirculation Pump
1. SERVICE PRO
MODEL 801P
CONTROL CENTER
12. PRIMARY AIR
ASSEMBLY
(Subassembly A5)
PRETREATMENT
CHAMBER
11. DIFFUSER
DROP PIPE
ASSEMBLY
(Subassemblies A2-A4)
10. MIXING BAR
DROP PIPE
ASSEMBLY
(Subassemblies
S8-S10)
9. MIXING BAR
(Subassembly S7)
Hydro-Kinetic
Installation and Operation Instructions
®
S1
S10
ANOXIC
CHAMBER
S9
S8
S7
8a. DIFFUSERS
(Subassembly A6)
7.
8.
9.
10.
11.
12.
S11
A5
S10
S12 S2
A4
S2
S9
AERATION
ANOXIC
AERATION
CHAMBER
CHAMBER
CHAMBER
A3
S8
A2
A6
A2
S7
A1
RECIRCULATION ASSEMBLY
8b. DIFFUSERS
(Subassemblies S1, (2) S2, S3,
(Subassembly A1)
FIGURE 1
Page 1
Intermediate Recirculation Assembly
Diffuser (2 required)
Mixing Bar
Mixing Bar Drop Pipe Assembly
Diffuser Drop Pipe Assembly (2 required)
Primary Air Assembly (2 required)
2. MODEL A150
AIR PUMPS
A5
S3
S4
S6
A4
S5
A3
(Subassemblies S5-S6)
CLARIFICATION
CHAMBER
7. INTERMEDIATE
S4, S11, S12)
RECIRCULATION
3. ALARM FLOAT
4. FLOW
EQUALIZATION
DEVICES
5. PRIMARY
RECIRCULATION
ASSEMBLY
6. MODEL SD103
PUMP

Advertisement

loading

Related Products for norweco HYDRO-KINETIC 3780L

This manual is also suitable for:

Hydro-kinetic 5670l