Haier 1U68MRAFRA-4 Service Manual page 34

Table of Contents

Advertisement

10.4.1
Thermistor or Related Abnormality
Indoor Display
Outdoor display
Method of
Malfunction
The temperatures detected by the thermistors are used to determine thermistor errors
Detection
When the thermistor input is more than 4.92V or less than 0.08V during compressor
Malfunction
operation.
Decision
Note: The values vary slightly in some models
Conditions
Supposed
Causes
Trouble
* Caution: Be sure to turn off power switch before connect or disconnect connector,
shooting
or else parts damage may be occurred.
Check the connector connection.
Thermistor resistance check
Thermistor resistance inspection method:
Remove the connector of the thermistor on the PCB, and measure the resistance of thermistor using tester. The
relationship between normal temperature and resistance is shown in the value of indoor thermistor.
E1: Room temperature sensor failure
E2: Heat-exchange sensor failure
LED1 flash 10 times Defrost temperature sensor failure
LED1 flash 11 times Suction temperature sensor failure
LED1 flash 12 times Ambient temperature sensor failure
LED1 flash 13 times Discharge temperature sensor failure
Faulty connector connection
Faulty thermistor
Faulty PCB
Is it normal?
Yes
Is it normal?
NO
Correct the connection
NO
Replace the thermistor
Yes
Replace the indoor PCB
32
Service Diagnosis
Domestic Air Conditioner