Warning Use this product only in the manner described in this manual. If the gas detector is used in a manner not specified by CTI, the protection provided by the gas detector may be impaired. To ensure your personal safety, read the Safety Information section before operating the gas detector.
WINGMAN Safety Information General Description The WINGMAN F1 portable gas detector is designed to protect personnel against amomonia gas • This is a gas detector, not an concentrations independent of fixed analytical measuring device. detection systems. • Don't use the detector if it is The large, lighted, LCD display shows damaged.
WINGMAN Display Elements Item Function Battery status Gas concentration value Alarm conditions Silence alarms / HIGH Calibration due* STEL CAL DUE Target gas Parts per million *During an alarm condition, this section of the display will show Silence. During normal operation, this section of the display will show Cal Due if the time since last calibration is ≥...
WINGMAN Pushbuttons Power Up Power Up: Hold for 1 second Power Down Power Down: Hold for 3 seconds Return Home Return Home: Tap ✅ Select Options will change depending on which menu is Next active. Silence Press △ 1 time for Peak/TWA/STEL △...
Once the self-test starts, it performs the following checks. Confirm that all actions occur. The screen will activate with "CTi" displayed SHUTTING All pixels of the display are turned on. DOWN Visual, audio, and vibrating alarms are activated.
WINGMAN User Options Calibration To enter the User Options menu Note: Before beginning calibration screens from the Home screen, press please ensure you have: Certified and hold the Calibration Gas, Zero Gas (optional), △ + ✅ keys for 1 second. Cal Cup, and Tubing attached to cup.
Page 11
WINGMAN Zero Calibration Span Calibration The current PPM value is displayed. If a The concentration of the Certified zero calibration is necessary, follow the Calibration Gas should be between ✅ next steps. Otherwise, press the 10% and 100% of the full-scale range to go to Span calibration.
WINGMAN Set Alarms CAL DONE ZERO -0.5% ALARMS SPAN 39.2% NEXT ▲ ▼ ENTER Note: If an extreme gain adjustment Once in the Set Alarms data screens, was applied, the sensor may be at or △ / ▽ press the keys to change the near the end of its useful life.
WINGMAN Set Clock Set the Time △ / ▽ Use the keys to set the Time ✅ (24-hour format). Use the key to advance through the screens. CLOCK SET TIME SET TIME ▲ HOURS MINUTES ▼ ENTER Set the Date ▲...
Use the keys from home screen to scroll through the various read only information screens. These screens ▲ contain what the WINGMAN F1's ▼ ENTER current settings are, periodic review is recommended to ensure changes have Once in the Event Log data screen, use △...
WINGMAN Responding to an Alarm Alarm modes: Low Alarm: • Slow flash • Slow beep • Low alarm flashes • Slow vibration HIGH HIGH High Alarm: STEL STEL • Fast alternating flash SILENCE SILENCE • Fast beep • High alarm flashes Alarm: During an alarm condition, •...
• Regular cleaning of the detector should only be done with a damp, soft cloth. Do not use The WINGMAN F1 portable gas solvents or chemicals. detector is designed for long life with •...
Turn off the detector before from CTI. proceeding. Electrochemical cells are extremely Use a small #1 Phillips head screwdriver to reliable, but several things can cause remove the (4) screws from the back of the detector and carefully open the case.
WINGMAN Battery Replacement Note: Ensure the sensor filter and audible alarm gasket are properly seated into the top half of detector housing. When the battery is removed from the Turn off the detector before detector, the clock will revert back to its proceeding.
No battery. Install battery. Dead battery. Replace battery. Reversed battery. Install battery correctly. Defective detector. Contact CTI. Displays more than Sensor still stabilizing. For new sensor element, allow 5 minutes 0 ppm in clean air. Need to re-zero. to stabilize.
Calibration Kit with valve, regulator, gauge for 34L RB34L-NH3/100 Certified Calibration Gas 100 ppm 34L Cylinder CK-CUP & HOSE-0 Cal gas cup and hose assembly Contact CTI to order: 920 N. Tradewinds Pkwy Columbia, MO 65201 phone: 866-394-5861 email: sales@ctigas.com...
WINGMAN Specifications: Detection Principle: Electrochemical Zero Drift: Less than 0.1% of full-scale Sampling Method: Diffusion per month, non-cumulative. Gases: Ammonia (NH3) Span Drift: Application dependent, but Range: 0-500 ppm generally less than 3% per month. Linearity: +/- 2% of full-scale. Display: LCD, HR TFT, 2.7"...
No goods shall of shipment to the buyer. This warranty be returned to CTI until receipt by the buyer of extends only to the sale of new and unused shipping instructions from CTI; and products to the original buyer.
Page 24
CT49-DOC1-0 ctigas.com | 866-394-5861 Software version 3.0.0 20230918...