novotechnik MUP-410 Instruction Manual

Digital din rail mounted signal converter

Advertisement

MUP-410
Digital DIN rail mounted signal
converter
INPUT FOR POTENTIOMETERS
IN 1
OUT 1
Pot.
OMNI
Input
Power
HAZARD OF ELECTRICAL SHOCK
- Disconnect all power and other supply lines before servicing equipment
Failure to follow this instruction may result in death or serious injury.
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.
No responsibility is assumed by Novotechnik Messwertaufnehmer OHG for any consequences arising out of the use of this device.
2

Connection

www.novotechnik.de
en
de
fr
es
fr
V
mA
DANGER
+
V
Analog
+
mA
output
-
-
Power supply
+
1

Description

cs
Input for potentiometers
Analog output
Up to 7 200 measurements/s
Quick configuration by DIP switch
it
PC configurable via USB port
Galvanic isolation 2.5 kVAC
Simple instalation to DIN rail
4
Hi
3
Lo
EQUIPMENT OPERATION HAZARD
- Do not use this product in safety critical system
- Do not disassemble, repair or modify this product
- Do not operate beyond the recommended operating environment
Failure to follow these instructions may result in death, serious injury, or equipment damage.
Note
Contactors, high power electric motors, frequency drives and other power devices
should not be in a close proximity of the meter. Input signal leads (measured value)
should be seperated from all power lines and power devices. Even though the device
has been designed and tested according to standards for industrial environment, we
strongly advise to adhere to the above presented rules.
1 / 4
LED Indication
Hi
Lo
Status
Device is running
1
Device functionality is limited, powered via USB
This device has a Delayed Start option
Error: device is out of order
2
Tare function is activated
Error: of input (> ±110% of range) or of sensor
[ERR.1, 3]
Error: AO loop open [ERR.10]
Error: setting / calibration [ERR.34-36]
Serious error (Safe mode) [ERR.50]
1
Button function is blocked
Simulation mode is activated
WARNING
0,05...2,5 mm
30...12 AWG
Ø 3,5 mm
Ø 0.14 in
MINI-TECHDOK - MUP-410_AO - 2023.1.7 - en
Legend
1
Connectors
2
Control button
3
RGB Status LED
2
8
0.32
1,5 Nm
13.2 lb-in

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MUP-410 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for novotechnik MUP-410

  • Page 1 Failure to follow these instructions may result in death, serious injury, or equipment damage. Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Novotechnik Messwertaufnehmer OHG for any consequences arising out of the use of this device. Connection...
  • Page 2 3. Set the tare by a long press (> 2 s) of the Hi button - LED Hi white, LED Lo green 4. Leave tare mode by a short press of the Hi button - LED Hi green, LED Lo white www.novotechnik.de 2 / 4 MINI-TECHDOK - MUP-410_AO - 2023.1.7 - en...
  • Page 3 Serious device error - damaged EEPROM. Send the device for repair. The device operates in an emergency mode, i.e. settings cannot be changed. Measurement error can be up to 5% www.novotechnik.de 4 / 4 MINI-TECHDOK - MUP-410_AO - 2023.1.7 - en...
  • Page 4 Novotechnik Messwertaufnehmer OHG Measuring instruments of the MUP-410 series conform to the European regulation 2014/30/EU, 2014/35/EU and 2011/65/EU, 2015/863/EU. Horbstrasse 12, 73760 Ostfildern, Germany This product must be installed, connected and used in compliance with prevailing standards and/or installation regulations.

Table of Contents