Trip unit protection

Advertisement

Trip Unit Protection Settings Adjustment for 140G2-K, 140G2-L, 140MG2-K, 140MG2-L
6
Dip LSIG Trip Unit
Notes-Note-Anmerkungen-Nota-Notas-注释
Ifault > I4 = Alarm
Example - Esempio - Beispiel - Exemple - 例子
In=600A
I4=600 x 0,55 = 330A
t4= 0,8s@ I>I4
7
Dip LSIG Trip Unit
Example - Esempio - Beispiel - Exemple - Ejemplo - 例子
InN= 100%In
Notes-Note-Anmerkungen-Nota-Notas-注释
Settings of neutral value (InN) to be obtained according to the following formula: I1 x InN < Iu
La regolazione del valore di neutro (InN) deve rispettare la seguente formula: I1 x InN < Iu
Die Einstellung des Werts des Neutralleiters (InN) anhand der folgenden Formel ausführen: I1 x InN < Iu
Le réglage de la valeur de neutre (InN) doit respecter la formule suivante: I1 x InN < Iu
El ajuste del valor del neutro (InN) debe cumplir con la seguente formula: I1 x InN < Iu
调节中性线 (InN) 时遵循以下公式: I1 x InN < Iu
Publication 140G-IN218A-EN-P - May 2021
Protection G- Protezione G- Schutzfunktion G - Proteção G- Protección G - G
Setting Neutral - Settaggio Neutro - Einstellung Neutralleiter -
Réglages Neutre - Configuraciones Neutro - 设定频率和中性
t
I4
t4
DIR 1002011A1516 (Version 00)
5
t=k
G
I