1. Introduction Thank you for purchasing the ZEUS three-phase online UPS system, FTP-230KSM/FTP-240KSM, from Forza. To enjoy all the features and benefits of this unit, please read and follow all installation and operation instructions thoroughly Please comply with all warnings and operating instructions in this manual. This equipment should only be in- before unpacking, installing or operating this device.
- Isolate the Uninterruptible Power Supply (UPS) - Then check for Hazardous Voltage between all terminals including the The Forza Zeus three-phase UPS system is available in the version and capacity as shown below: protected earth. Risk of Voltage Backfeed...
2-2. UPS–floor-anchoring 1. RS-232 communication port (only for firmware updates) 2. USB communication port 3. Emergency power off function connector (EPO connector) NOTICE: The L-shaped floor anchoring brackets that secured the enclosure to the pallet during shipment may be used Note: Keep the EPO connector closed for UPS normal operation.
2) For safety considerations, turn off the mains switch in the building before installation. 3) Turn off all the devices before connecting them to the UPS. 4) Wiring sizes should be installed in accordance with the following table: CAUTION - To reduce the risk of fire, AC input terminals of each UPS should be connected to a branch circuit breaker with maximum overcurrent protection in accordance with the National Electric Code, ANSI/NFPA 70 as listed in the table below.
4. When your computer restarts, the management software will appear as a green plug icon located in the system tray, near the clock. 5. To access the Forza Tracker management software as an administrator, you must enter the password: 111296. 6) Refer to the following communication wiring diagrams for current sharing cable and parallel cable connections...
3. Advanced operation 3-3. Main menu screen After initialization, the LCD will display the main screen. There are five sub-menus: Control, value, setting, information 3-1. Initial setup and data log. Touch any sub-menu icon to enter into the sub-screen. 1) Before operating the unit, make sure that the two strings of batteries are properly wired with the positive, GND, and negative terminals connected in this order, and that the breaker of the battery pack is in its “ON”...
Page 8
After initialization, the main screen will be displayed as shown below. On the bottom, there are five icons representing UPS On/Off five sub-menus: CONTROL, VALUE, SETTING, INFO, DATALOG. It will display Turn on UPS? when the unit is off. It will display Turn off UPS? when the unit is on. Touch YES to turn the UPS on or off.
Page 9
Audio mute 3-3-3. Value screen Touch the icon to enter the Value page. Touch the icon to browse through the information. When audio is enabled, Mute all appears on the screen. Select Yes to mute the unit. If Mute all is active, the icon will appear on the top left corner of the main screen.
Page 10
Permission list: UPS operation mode Authorization Standby Bypass Battery Battery test Converter Line mode Fault mode mode mode mode mode mode mode Setting item User Technician password Date/Time Language Input source Contact Phone Mail Audio alarm Output voltage Output frequency CVCF mode Value screen - Page 3 Bypass forbid...
Page 11
GENERAL ADVANCE General screen - Page 1 Advanced- Password page • Date/Time: Sets the date and time. The format is YYYY-MM-DD HH:MM:SS. The calendar day will be automatically A password (4 digits) is required to access the ADVANCE page. changed when the year, month and date are set. •...
Page 12
ELECTRICAL • Bypass at UPS off: Select the bypass status when manually turning off the UPS. This setting is only available when Bypass forbid is set to Disable. - Enable: Bypass enabled. When selected, the bypass mode is active. - Disable: Bypass disabled. When selected, there will be no output through bypass when manually turning off the UPS.
Page 13
MISCELLANEOUS SYS PARAMETER Miscellaneous setting page SYS PARAMETER - Page 1 • Auto restart - Enable: If this option is selected, when the UPS shuts down due to low battery, the UPS will return to line mode • Model Name: Identifies the UPS model. once utility power is restored.
Page 14
INSTALL INFO VOL CALI - Page 2 INSTALL INFO Page • Line VOL: Line voltage calibration. Increments per click is 0.1%, with either the Up or Down key . Press the Up key • SYS Install Date: Sets the date of the UPS installation. to increase 0.1% and press the Down key to decrease 0.1%.
Page 15
CURR CALI CURR CALI Page INITIAL PARAMETERS Page • Output CURR: Output current calibration. Increments per click is 0.1%, with either the Up or Down key. Press the • PARAMETERS: When you press this option, a confirmation window will be displayed as shown in the image above. Up key to increase 0.1% and press the Down key to decrease 0.1%.
Page 16
ELECTRICAL INITIAL EEPROM page Electrical setting - Page 1 • EEPROM: When you press this option, a confirmation window will be displayed as shown in the image above. Touch YES to clear all EEPROM values. Touch Back or No to cancel this operation and return to the INITIAL menu page. •...
Page 17
• Bypass at UPS off: Select the bypass status when manually turning off the UPS. This setting is only available when MISCELLANEOUS Bypass forbid is set to Disable. - Enable: Bypass enabled. When selected, the bypass mode is active. - Disable: Bypass disabled. When selected, there will be no output through bypass when manually turning off the UPS.
Page 18
3-3-5. Information screen Touch the icon to open the information page. Touch the icon to browse the information. Touch the icon to return to main screen. Touch the icon to go back to the previous menu. Rated information page Rated information •...
3-3-6. Data Log screen Touch the icon to open the data log page. Data log is used to record the warning and fault information of the UPS. The record contains date and time, code, type, and description. Touch the icon to move up or down the page if there is more than one in the data log.
3-5. Single UPS operation 5. Battery mode operation 1) When the UPS is in Battery mode, the buzzer will beep according to the battery capacity. 1. Turn on the UPS with utility power (in AC mode) a. If the battery capacity is more than 25%, the buzzer will beep once every 4 seconds. b.
11. Operation in Fault mode 2) Make sure all of the UPS units are the parallel models and follow the wiring scheme in section 2-5. 3) Install the new parallel system as per section 2-6. 1) When the buzzer beeps continuously, it means that there is a fatal error in the UPS. (Fault codes are available in the 3.
3-7. Fault codes 3-8. Warning codes Fault code Fault event Icon Warning Warning Warning event Warning event Bus start failure None code code Bus over None Battery unconnected Line issues are different in a parallel system Bus under None IP Neutral loss Bypass issues are different in a parallel system Bus unbalance None...
4. Troubleshooting guide 5. Storage and Maintenance If the UPS system does not operate correctly, use the table below to troubleshoot the problem. 5-1. Storage Charge the UPS for at least 7 hours before storing the unit. Cover the UPS, and place it upright in a cool, dry location. Symptom Possible cause Solution...