3. Protective zone
(4) When installed in a location where only the front opened (building walls on both sides)
Where the distance between both sides of the unit and the wall is more than 1 m, define the protective zone as fol-
lows: (Fig. 3-5)
- 1 m to the sides and to the front of the unit
- the rear of the unit to the wall
- 0.3 m from the ground.
en
0.3 m
Where the distance between both sides of the unit and the wall is less than 1 m, define the protective zone as follows:
(Fig. 3-6)
- from the both sides of the unit to the wall
- 2.5 m to the front of the unit
- the rear of the unit to the wall
- 0.3 m from the ground.
Where the distance between one side of the unit and the wall is less than 1 m, same conditions as shown in Fig. 3-4
apply.
16
1 m
1 m
1 m
Fig. 3-5
0.3 m
˂ 1 m
˂ 1 m
2.5 m
Fig. 3-6