Leakage Test And Evacuation; Preparation; Leakage Test - LG ZUAA1 Installation Manual

Hide thumbs Also See for ZUAA1:
Table of Contents

Advertisement

Available languages

Available languages

LEAKAGE TEST AND EVACUATION

- Pressure in the system rises.
- Operating current rises.
- Moisture in the refrigerant circuit may freeze and block capillary tubing.
- Water may lead to corrosion of parts in the refrigeration system.
Therefore, the indoor/outdoor unit and connecting tube must be checked for leak tight, and vacu-
umed to remove incondensible gas and moisture in the system.

Preparation

- Check that each tube (both liquid and gas side tubes) between the indoor and outdoor units
have been properly connected and all wiring for the test run have been completed. Remove the
service valve caps from both the gas and the liquid side on the outdoor unit. Check that both the
liquid and the gas side service valves on the outdoor unit are kept closed at this stage.

Leakage test

- Connect the manifold valve (with pressure gauges) and dry nitrogen gas cylinder to this service
port with charge hoses.
!
CAUTION
Be sure to use a manifold valve for leakage test. If it is not available, use a stop valve for this
purpose. The "Hi" knob of the manifold valve must always be kept close.
- Pressurize the system to no more than 3.8(551) MPa(psi) with dry nitrogen gas and close the
cylinder valve when the gauge reading reached 3.8(551) MPa(psi) Next, test for leaks with liquid
soap.
!
CAUTION
To avoid nitrogen entering the refrigerant system in a liquid state, the top of the cylinder must
be higher than its bottom when you pressurize the system. Usually, the cylinder is used in a ver-
tical standing position.
LEAKAGE TEST AND EVACUATION
21

Advertisement

Table of Contents
loading

Table of Contents