Mitsubishi Electric MXZ-2HA40VF2-E1 Service Manual page 53

Table of Contents

Advertisement

12-4. TROUBLESHOOTING CHECK TABLE
MXZ-2HA
Symptom
Indication
No.
LED1(Red) LED2(Yellow)
Outdoor unit
1
Lit
Once
does not
operate.
2
Lit
Twice
3
Lit
3 times
4
Lit
4 times
5
Lit
5 times
6
Lit
7 times
7
Lit
17 times
'Outdoor
unit stops
Twice
Not lit
and restarts
8
3 minutes
later' is
repeated.
3 times
Not lit
9
10
4 times
Not lit
11
5 times
Not lit
12
9 times
Not lit
13
13 times
Not lit
14
8 times
Not lit
10 times
Not lit
15
Outdoor unit
operates.
16
Once
Lit
Twice
Lit
17
18
3 times
Lit
19
4 times
Lit
OBH828D
Abnormal point / Condition
The indoor unit detects an abnormality in the LEV and drain pump.
LEV and drain pump
Overcurrent protection cut-out operates 3 consecutive times
within 1 minute after the compressor gets started.
Outdoor power system
A short circuit is detected in the thermistor during operation, or when an
Discharge temperature
open circuit is detected in the thermistor after 10 minutes of compressor
thermistor
startup.
Fin temperature
thermistor
A short or open circuit is detected in the thermistor during operation.
P.C board temperature
thermistor
Ambient temperature
A short or open circuit is detected in the thermistor during operation.
thermistor
A short circuit is detected in the thermistor during operation, or when
Outdoor heat exchanger
an open circuit is detected in the thermistor after 5 minutes (in cooling)
temperature thermistor
and 10 minutes (in heating) of compressor startup.
A short circuit is detected in the thermistor during operation, or when an
Defrost thermistor
open circuit is detected in the thermistor after 5 minutes of compressor
startup.
The nonvolatile memory data cannot be read properly.
Nonvolatile memory data
A closed valve and air trapped in the refrigerant circuit are detected
Outdoor refrigerant
based on the temperature sensed by the indoor and outdoor thermistors
system abnormality
and the current of the compressor.
18 A current flows into intelligent power module.
Overcurrent
Discharge temperature
Discharge temperature exceeds 116°C during operation. Compressor can
protection
restart if discharge temperature thermistor reads 100°C or less 3 minutes
later.
Fin temperature
The fin temperature exceeds 90°C during operation.
protection
P.C. board temperature
The P.C. board temperature exceeds 78°C during operation.
protection
The outdoor heat exchanger temperature exceeds 70°C during cooling
High pressure
or indoor gas pipe temperature exceeds 70°C during heating.
protection
The bus-bar voltage exceeds 430 V or falls to 50 V or below during
Bus-bar voltage
compressor operating.
protection
Failure occurs 3 consecutive times within 30 seconds after the fan
Outdoor fan motor
gets started.
Current sensor
A short or open circuit is detected in the current sensor during
protection
compressor operating.
Compressor
The compressor does not synchronize with the operating power.
Primary current protection
The input current exceeds 10 A.
Secondary current protection
The current of the compressor exceeds 17 A.
High pressure protection
The indoor gas pipe temperature exceeds 45°C during heating.
Defrosting in cooling
The indoor gas pipe temperature falls 3°C or below during cooling.
The discharge temperature exceeds 100°C during operation.
Discharge temperature
protection
The frequency of the compressor is kept 80 Hz or more and the discharge
Low discharge
temperature is kept under 50°C (COOL mode)/40°C (HEAT mode) for
more than 40 minutes.
temperature protection
Condition
53
Remedy
• Refer to 12-6.
"Check of LEV".
• Check the drain pump of the indoor unit.
• Check the connection of the compressor connecting
wire.
• Refer to 12-6.
"How to check inverter/compressor".
• Check the stop valve.
• Refer to 12-6.
"Check of outdoor thermistors".
• Refer to 12-6.
"Check of outdoor thermistors".
• Replace the inverter P.C. board.
• Refer to 12-6.
"Check of outdoor thermistors".
• Replace the inverter P.C. board.
• Check for a gas leak in a connecting piping etc.
• Check the stop valve.
• Refer to 12-6.
"Check of outdoor refrigerant circuit".
• Reconnect compressor connector.
• Refer to 12-6.
"How to check inverter/compressor".
• Check the stop valve.
• Check the amount of gas and the refrigerant circuit.
• Refer to 12-6.
"Check of LEV".
• Check the refrigerant circuit and the refrigerant amount.
• Refer to 12-6.
"Check of outdoor fan motor".
• Check the amount of gas and the refrigerant circuit.
• Check the stop valve.
• Replace the inverter P.C. board.
• Refer to 12-6.
"Check of outdoor fan motor".
• Replace the inverter P.C. board.
• Reconnect compressor connector.
• Refer to 12-6.
"How to check inverter/compressor".
• Check the stop valve.
These symptoms do not mean any abnormality of the
product, but check the following points.
• Check if indoor filters are clogged.
• Check if refrigerant is short.
• Check if indoor/outdoor unit air circulation is short cycled.
• Check the refrigerant circuit and the refrigerant amount.
• Refer to 12-6.
"Check of LEV".
• Refer to 12-6.
"Check of outdoor thermistors".
• Refer to 12-6.
"Check of LEV".
• Check the refrigerant circuit and the refrigerant amount.

Advertisement

Table of Contents
loading

Table of Contents