(eventually this access can be password locked) in order to deactivate the ‘SOS mode’. Deactivation of ‘SOS mode’ must be performed manually by configuring the function to ‘oFF’. To configure the ‘SOS mode’ function, see section 16.9. w w w. fema . es...
‘uSEr’. • Code ‘---’ identifies the end of the list, it follows code ‘199’ and the list continues with code ‘010’. Select ‘---’ exits the ‘configuration menu’ without applying changes. FEMA · MANUFACTURING FOR INDUSTRIAL AUTOMATION...
Others common signal Vexc common +Vdc 0/10 Vdc common +Vdc Terminal 4 and terminal 1 are internally connected. Connecting dangerous voltages to terminal 4 makes terminal 1 a terminal with dangerous voltage. 7 8 9 w w w. fema . es...
‘On ‘Sq’’ parameter (see section 16.9). When the operator exits the ‘configuration menu’, the output Flashing signal is temporarily set to minimum value for a time <5 seconds, while the instrument restarts. FEMA · MANUFACTURING FOR INDUSTRIAL AUTOMATION...
‘force’ menu, the messages associated to the ‘LE’ (3) key, activate filters, password function, etc. See section 16 for a detailed explanation on the ‘configuration menu’. w w w. fema . es...
1 2 3 1 2 3 Terminal 4 and terminal 1 are internally connected. Connecting dangerous voltages to terminal 4 makes terminal 1 a terminal with dangerous voltage. +8.2 Vexc signal signal common NAMUR Pick-up FEMA · MANUFACTURING FOR INDUSTRIAL AUTOMATION...
(see section 16.2). Parameters not available in the active mode, will Namur 5.1 KOhms ±30 Vdc show ‘-nA-’ when accessing their value at the configuration menu. 5.1 KOhms ±30 Vdc ‘0’ level <1V, ‘1’ level >2V <600 Vac 900 KOhms 800 Vac <60 Vac 340 KOhms 200 Vac w w w. fema . es...
. Gain applies only to signals through channel ‘A’ and connected 5 Vdc to terminals ‘123’. disabled • select ‘G__1’ to activate the gain ‘1’. Usual gain for Vdc signals, that are correctly detected operating the ‘trigger level’. FEMA · MANUFACTURING FOR INDUSTRIAL AUTOMATION...
‘Advanced scaling’ (Ad.Sc) parameters (see section 16.5). 0/600 Hz • example: select the ‘1 KHz ’ input range and to customize to a smaller 0/800 Hz range (for example 0/750 Hz or 250/750 Hz) see section 16.5 and operate each parameter. 0/1 KHz w w w. fema . es...
‘Process low’ (Pr.Lo) parameter, configure the process value associated to the low input signal value. • at the ‘Process high’ (Pr.hI) parameter, configure the process value associated to the high input signal value. FEMA · MANUFACTURING FOR INDUSTRIAL AUTOMATION...
‘0’ is the value assigned to the ‘input signal low’ parameter, and ‘100’ is the value assigned to the ‘input signal high’ parameter (see section 16.5) (for example : ‘Prct 23.5’ when the reading is 23.5% of the full scale). w w w. fema . es...
Select the value from 0 to 100% of the active output range (4/20 mA or 0/10 Vdc). To deactivate the ‘SOS mode’ select ‘oFF’. See section 6 for more information on the ‘SOS mode’. FEMA · MANUFACTURING FOR INDUSTRIAL AUTOMATION...
Page 15
‘configuration menu’. The password does not block access to the ‘force’ menu. To deactivate the password, select ‘oFF’. • at the ‘Factory reset’ (FAct) parameter select ‘yes’ to activate the default factory configuration (see section 18 for a list of factory default parameters). w w w. fema . es...
Page 17
Display output signal value information label Average filter 0 to 100 process value signal percentage ‘Dead band’ 0.0 to 100.0% Version Key ‘UP’ Force low (‘force’ menu) Password Force high Factory reset Force set w w w. fema . es...
• the leds light a round shape while the new configuration is applied • the start up message appears (‘SEnSor nPn 1.000 kHz’) • the actual signal input value is displayed • the instrument is in ‘normal mode’ of operation FEMA · MANUFACTURING FOR INDUSTRIAL AUTOMATION...
Within the warranty period and after examination by the manufacturer, the unit will be repaired or substituted when found to be defective. Extended warranty available at (see section 3) w w w. fema . es...