Page 1
Quick guide Installation guidelines Power Quality Analyser multimess F144-PQ In our download center you will find the System english appropriate instructions for KBR devices. https://www.kbr.de/de/dienstleistungen/ download-center...
Meaning of the symbols used on the device ..............8 Commissioning ..........................9 KBR Kompensationsanlagenbau GmbH does not accept any liability for any loss or damage resulting from printing errors in or changes to this manual. In addition, KBR Kompensationsanlagenbau GmbH does not accept any liability for any loss or damage caused by defective devices or devices manipulated by the user.
Page 3
Table of contents multimess F144-PQ Summary description ................9 Lieferumfang ........................... 9 Fitting ...............................10 Protection earth ...........................11 Supply voltage ..........................12 Mains connection for multimess F144-PQ .................14 3.6.1 3-phase / 4-wire connection ....................15 3.6.2 3-Phase / 4-wire connection without neutral current ............17 3.6.3...
The company KBR Kompensationsanlagenbau GmbH does not accept any liability for damage or loss of any kind resulting from faulty devices or from devices that have been modified by the user.
Introduction Safety Safety Instructions IT IS IMPORTANT FOR PERSONAL SAFETY TO FOLLOW THESE INSTRUCTIONS. THESE INSTRUCTIONS MUST BE KEPT IN A SAFE PLACE! Observe operating instructions. Always keep the operating instructions with the appliance. Ensure that the machine is only operated in perfect condition. ...
Introduction Structure of the warnings Warnings are structured as follows: Nature and source of the danger! Consequences if not observed. SIGNAL WORD Steps to avoid the danger. Graduation of warnings Warnings differ according to the type of danger as follows: Warns of an imminent danger which, if not avoided, will result in death or serious injury.
All technical connection values and rated data must be observed! The multimess F144-PQ is suitable for the following installation location and should, should only be operated in this environment.
Introduction Cleaning Use a soft, slightly moistened and lint-free towel. Make sure that no moisture penetrates the housing. Do not use window cleaners, household cleaners, sprays, solvents, cleaners containing alcohol, ammonia solutions or scouring agents for cleaning. Please use only water for cleaning.
The multimess F144-PQ can be used as a Power Quality Interface according to power quality standards such as IEC61000-2-2 / EN50160 or to check the technical con-nection guidelines such as DIN VDE AR 4110 and DIN VDE 4120 and many more.
For mounting the multimess F144-PQ, four mounting brackets are included in the scope of delivery. These must be snapped into the housing of the multimess F144-PQ at all four corners (see picture below). The clamps must then be screwed against the panel with a maximum torque of five Nm using an Allen key (2.5 mm) on the back of the PQI-DE to...
Commissioning Protection earth The device has a protective earth, which also serves as reference potential for the voltage inputs. The protective earth is marked with and terminal X1 / 13 on the measuring instrument. Connect the earth cable to terminal X1 / 13 on the meter and tighten the screw. Use an eyelet terminal for the connection and make sure it is tight! Danger to life due to electric shock! DANGER!
Commissioning Supply voltage The multimess F144-PQ is available in two different supply voltage versions. Please take the correct supply voltage from the type label before connection. Example of connection to 230 V AC After connecting and switching on the power supply, the status LED lights up red, changes to green and the display starts in the commissioning wizard.
Page 13
Commissioning Material damage due to non-observance of the NOTICE! connection conditions or impermissible overvoltage! Failure to comply with the connection conditions or exceeding the permissible voltage range may damage or destroy your device. Before applying the supply voltage to the device, the following points must be observed: ...
Commissioning Mains connection for multimess F144-PQ The mains connection of the multimess F144-PQ depends on the type of mains in which the measurement is to be made. The multimess F144-PQ is designed for direct measurement in low voltage (3 phase / 4 wire connection) for low voltage networks (TN, TT and IT networks) or for residential and industrial applications.
Commissioning 3.6.1 3-phase / 4-wire connection Example of a connection for a multimess F144-PQ in a three-phase four-wire system Voltage connections The voltage connections must be made as shown in the circuit diagram above If no N conductor connection is available, connect connections E and N together.
Page 16
Attention dangerous contact voltage! Flashover and high short-circuit currents possible in CAT III and CAT IV! Ensure that the PE conductor (earthing) is connected to the multimess F144-PQ. Before starting work, check that no voltage is present! Provide protective equipment for CAT II, CAT III or CAT IV.
If no neutral conductor current is available in the 3-phase / 4-wire net-work, the S2 current inputs of the multimess F144-PQ must all be short-circuited and the S2 terminals of the current transformers used must be connected to S1 (terminal X6:67).
Attention dangerous contact voltage! Flashover and high short-circuit currents possible in CAT III and CAT IV! Ensure that the PE conductor (earthing) is connected to the multimess F144-PQ. Before starting work, check that no voltage is present! Provide protective equipment for CAT II, CAT III or CAT IV.
3-phase / 3-wire connection 3.6.4.1 Connection tranformer for feature multimess F144-PQ in 3-wire connection for medium and high-voltage via transformer Voltage connections Make sure that the measuring cable N / E is connected to terminal 34 for each measurement.
Commissioning 3.6.4.2 Connection to voltage sensors multimess F144-PQ in 3-wire connection for medium and high-voltage via voltage sen- sors Voltage connections Ensure that terminals 37 & 38 (N/E) are short-circuited for each measurement. Ensure that the shielding of the voltage sensors is grounded on both sides.
Attention dangerous contact voltage! Flashover and high short-circuit currents possible in CAT III and CAT IV! Ensure that the PE conductor (earthing) is connected to the multimess F144-PQ. Before starting work, check that no voltage is present! Provide protective equipment for CAT II, CAT III or CAT IV.
Operation of the multimess F144-PQ Getting started When the power analyser multimess F144-PQ is put into operation for the first time, the instrument will appear in a guided “Wizard“ mode. The operator is automatically guided through the initial commissioning of the instrument. This Wizard must be performed once after the PQ meter has been fully connected.
Parameterization First commissioning - wizard - procedure 4.3.1 Wizard setting Language Selection of display language Setup wizard Language English 4.3.2 Wizard setting Power Quality standard Selection of the Power Quality standard Setup wizard PQ standard Press the key to switch between the following.
Parameterization 4.3.3 Wizard setting Net type Basic settings / network connection Setup wizard The net type form cannot Net type be edited if the PQ standard EN50160-LVIT or EN50160-MV/HV 4 cond, 3 phase is selected! For more information about the network connection, see Chapter Hardware connec- tion ...
Parameterization 4.3.5 Wizard setting Voltage Transformer Primary Voltage: Setup wizard Corresponds to the primary rated voltage of Voltage transformer the voltage transformer. primary Voltage [V] P-P Sec. Voltage: 20000.00 Corresponds to the secondary rated voltage of the voltage transformer..
Parameterization 4.3.7 Wizard setting Current Transformer Primary Current: Setup wizard Primary nominal current of the connected Current transformer current transformer. primary Current [A] Sec. Current: 3000 Secondary nominal current of the connected current transformer. The voltage transformer factor is Setup wizard calculated automatically! Current transformer...
Parameterization 4.3.9 Wizard setting Date, Time and Timezone Manual entry of date and time as local time. Setup wizard Furthermore the local time zone must be entered and if the device should calculate the Date changeover for summer / winter time by its own .
Subnet mask Entering the subnet mask 255.168.0.1 Gateway: Entering a gateway In the factory setting, the Setup wizard multimess F144-PQ is factory pre-set with the IP address Gateway 192.168.56.95 and the subnet mask 255.255.0.0. 192.168.0.1 ...
Parameterization 4.3.11 Wizard setting Security Mode Security Mode: Setup wizard Active: high security mode The device is set up in security mode. Security mode Communication is encrypted and device access is protected. The completion of the active commissioning in security mode requires the setup of the necessary user accounts and must be completed with the software WinPQ or...
Parameterization The separate security docu- mentation for administrators describes all security-relevant system settings for setting up and operating the device and the entire PQ system (requirement of the BDEW Whitepaper). In the active security mode it is recommended Lock menu to password the display in addition to the encryption.
Technische Daten Technical Data Dimensions / Weight Dimensions / Weight: (L x B x H) 144 x 144 x 90 mm without terminals 144 x 150 x 110 mm with terminals Outbreak size:: 138 x 138 mm (+0,8 mm) Weight: 1220 g Electrical safety –...
Technical data Power supply Merkmal AC Nominal range 100 – 240 V AC Operating range 90 – 264 V DC Nominal range 120 – 320 V 24 – 60 V DC Operating range 108 – 350 V 18 – 75 V Power consumption ≤...
Technical data Current Inputs Current Inputs Channels I1, I2, I3, IN/4 Electrical safety 300 V CAT III Input type Differential, isolated Impedance ≤ 4 mΩ Nominal input current I Full scale range (FSR) 10 A Overload capacity permanent 20 A ≤...
Technical data Binary outputs Binary outputs (BO) 4 binary outputs 3 x closer 1 x changeover Contact specification (EN60947-4-1, -5-1) Configuration 3 x SPST (Single Pole Single Throw) 1 x SPDT (Single Pole Double Throw) Nominal voltage 250 VAC Nominal current Nominal load AC1 1500 VA Nominal load AC15, 230 VAC...
Technical data Electrical safety Electrical safety – IEC 61010-1 – IEC 61010-2-030 Protection class Pollution degree Overvoltage category mains supply option: 300 V / CAT II 150 V / CAT II Measurement category 300 V / CAT IV 600 V / CAT III Altitude ≤...