Page 1
Online Fixed Gas Detector GD300:XX Instruction Manual Notice to Reader Please read this instruction manual before using the detector www.gasdog.com +86 773-280-9002 sales@gasdog.com...
The user should keep the factory certificate properly, and the warranty period is subject to the date on the certificate. Please pay attention to attach the factory certificate when returning for repair. www.gasdog.com +86 773-280-9002 sales@gasdog.com...
H. The instrument should be protected ≤2CM Cable from damp and rainwater inflow, which will affect the internal circuit board. 8.8.8.8 IR AL AH The wiring recommendations are shown in the diagram below. ≥30CM Figure H www.gasdog.com +86 773-280-9002 sales@gasdog.com...
Page 5
Note: The pipe-mounted type requires that the inside of the pipeline is normal temperature and pressure (temperature -20~50℃, pressure 0.1mPa) and humidity ≤95%RH. If the above conditions are not met and this installation method is required, please contact the manufacturer for a solution. www.gasdog.com +86 773-280-9002 sales@gasdog.com...
Page 6
Instrument Dimensions and Mounting Hole Map ● Apperance and installation hole map 89.00 140.00 φ8.00 φ8.00 φ8.00 118.00 ● Apperance and installation hole map of gas detector with alarm light 89.00 179.00 φ8.00 φ8.00 φ8.00 118.00 www.gasdog.com +86 773-280-9002 sales@gasdog.com...
The loop length indicates the total length of the positive and negative wires of the power supply, and the actual length of the cable is equal to half of the loop length. www.gasdog.com +86 773-280-9002...
Page 8
R: Maximum load resistance(Ω) (500Ω when powered by 24V, including control system input resistance and cable internal resistance) Rc: input resistance of the control system (the input resistance of our controller is 50Ω) ρ: core resistivity (copper: 1.85×10ˉ Ω·mm ) S: core cross-sectional area(mm ) www.gasdog.com +86 773-280-9002 sales@gasdog.com...
Page 9
COM:Common 24V:24+,positive RS485A RS485B GND:24-,negative 4~20mA:4~20mA analog Alarm Motherboard connector JP1 signal Digital probe portDigital probe port Note: Do not connect wires with power on at any time. * High alarm relay (Optional) . Wiring diagram www.gasdog.com +86 773-280-9002 sales@gasdog.com...
Make sure the instrument is in clean air environmrnt (do not do this in a non-clean air environment). Note: After the zero point calibration, the instrument reading will automatically return to zero (oxygen 20.93% VOL, nitrogen 78.1% VOL, carbon dioxide 450ppm). Power on when ready. www.gasdog.com +86 773-280-9002 sales@gasdog.com...
Page 11
This operation is mainly divided into two steps: [Set Calibration Point] and [Span Calibration]. Note: After the calibration, please remove the calibration cap. Do not install the calibration cap on the detector during testing. Flowmeter detector Calibration Empty www.gasdog.com +86 773-280-9002 sales@gasdog.com...
Page 12
3. Press the "OK" key again to enter the function interface. After adjusting the "0" displayed on the interface to “1 " by the "+" key, press the "OK" key again to display the current detection reading. IR AL AH IR AL AH www.gasdog.com +86 773-280-9002 sales@gasdog.com...
(without pressing the "OK" key to confirm the operation) will not be saved in the EEPROM. The parameters used are still the previous values when restarted again. www.gasdog.com +86 773-280-9002 sales@gasdog.com...
Page 14
1:Non-standard version (old protocol) protocol Note: F-06 and below operations do not need to be operated under normal circumstances, and only professionals can operate when necessary. F-11 to F-19 are reserved functions, please consult the manufacturer for details. www.gasdog.com +86 773-280-9002 sales@gasdog.com...
A. 4-20mA current signal output connection mode. (must be grounded together) Control panel DCS or PLC Ch-1 4-20mA Ch-2 Ch-N 24V,DC B. RS485 digital signal output connection mode 1. (can be independently grounded) Control panel DCS or PLC RS485A RS485B 24V,DC www.gasdog.com +86 773-280-9002 sales@gasdog.com...
Page 17
C. RS485 digital signal output connection mode 2. (can be independently grounded) software RS485A RS485 RS485B to USB 24V,DC www.gasdog.com +86 773-280-9002 sales@gasdog.com...