Introduction; Before You Begin; Shipment Contents; Software - Gallagher HBUS 16 In 16 Out Board Installation Manual

In 16 out board
Table of Contents

Advertisement

ATTENTION: This equipment contains components that can be damaged by electrostatic
discharge. Ensure both you and the equipment are earthed before beginning any servicing.
IMPORTANT: The Gallagher HBUS 16 In 16 Out Board can only be used with Gallagher
Command Centre vEL7.20 software (or later). Earlier versions of Command Centre do not
support this device.

1 Introduction

The Gallagher The Gallagher HBUS 16 In 16 Out Board extends the existing connectivity of the Gallagher
Controller 6000 via the HBUS communications protocol. The board provides connection for 16 inputs and
16 outputs.
The HBUS 16 In 16 Out Board is supplied as a single circuit board, designed to fit into a Gallagher Cabinet.
It is designed to connect to a Controller 6000. The blue coloured PCB signifies HBUS for ease of
identification. A centrally located tamper detector provides front and rear optical tamper detection.

2 Before you Begin

2.1

Shipment Contents

Check the shipment contains the following items:
1 x Gallagher HBUS 16 In 16 Out Board
1 x Gallagher HBUS 16 In 16 Out Board installation note (3E3473)
1 x Gallagher HBUS 16 In 16 Out Board component identification decal (3E3577)
32 x 4k7 ohm resistors
2.2

Software

The HBUS I/O device software is factory-loaded prior to shipment. New device software for the
HBUS 16 In 16 Out Board is automatically downloaded from the Controller 6000 vGR7.20//b672
(or later).
To view the version of device software, as last reported by the board itself, click the Connections
tab of the HBUS I/O item in Command Centre.
Note: The HBUS I/O item will display as offline until the item is fully configured.
2.3

Power Supply

Gallagher HBUS 16 In 16 Out Board requires a 13.6 Vdc + 15% power supply. This is connected
through the terminals labelled Vin and GND. An onboard 2 A resettable polyfuse provides over
current protection.
The size of the DC cable supplying the HBUS I/O Devices and any other connected equipment,
(e.g. readers, detectors, locks, etc.) must be of sufficient size to ensure that the voltage at the
Gallagher HBUS 16 In 16 Out Board is never below 13.6 Vdc - 15% (11.56 volts).
Note: It is recommended that lock power be supplied via a separate cable from the control
electronics, to minimise the possibility of high current spikes resulting from lock switching
causing other electronic equipment to malfunction.
3E3473 Gallagher HBUS 16 In 16 Out Board Installation Note | Edition 10 | January 2021
Copyright © Gallagher Group Limited
Page 4