CAUTION:
Disconnect power supply before wiring connections are made or service to avoid possible electrical shock or damage
to equipment.
Do never touch live parts with your ngers or with any tool.
Please note: scale in KP units is indicative only. For accurate
setting or when using according to FM approval use additional
pressure gauge to set the unit.
Contact system with standard AG contacts
Single pole changeover switch (SPDT).
Alternating current:
AC-1:
16 A, 400 V
AC-3:
16 A, 400 V
AC-15:
10 A, 400 V
Direct current:
DC-13:
12 W, 220 V
2
When used acc. to UL or FM regulations
Voltage
AC
240
120
Use copper wire only
Tightening torque 20 lb. in.
Contact system with gold contacts
Single pole changeover switch (SPDT): 1...30 mA, 5...30 V DC.
Contact load when Au surface isburned away:
Alternating current:
AC-1:
10 A, 400 V
AC-3:
6 A, 400 V
AC-15:
4 A, 400 V
Direct current:
DC-13:
12 W, 220 V
IC.PI.P10.E3.02 / 520B5882
Listed refrigeration
controller 61B5
FL
LR
Resist.
DC
A
A
lead
8
48
8A
16
96
16A
240
© Danfoss A/S (AC-MCI / jmn), 2013-11
Pilot
duty
3A
12W