INSTRUCTION MANUAL
PARAMETER GENERATOR
BEFORE USE ....
Thank you for choosing us. Before use, please check con-
tents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact our sales office or representatives.
■ PACKAGE INCLUDES:
Signal conditioner (body + base socket) .............................(1)
■ MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■ POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and
confirm its operational range as indicated below:
AC power: Rating ±10%, 50/60 ±2 Hz, approx. 2VA
DC power: Rating ±10%, approx. 2.5W
or 85 – 150V, approx. 2.5W for 110V rating
■ GENERAL PRECAUTIONS
• Before you remove the unit from its base socket or mount
it, turn off the power supply for safety.
■ ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -5 to +60°C
(23 to 140°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
■ WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■ AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
MODEL
COMPONENT IDENTIFICATION
Body
Connection Diagram
Front Cover
LCD Meter
(optional)
Specifications
■ HOW TO OPEN THE FRONT COVER:
Hang your finger on the hook at the top of the front cover
and pull.
The shape of base socket may be different
for some models.
■ STANDARD TYPE: MONITOR JACKS
• Monitor jacks for setpoint adjustment
0 – 10V DC is output in proportion to 0 – 100% output set-
points. Insert a tester with a diameter of 2.0 mm (.08") into
the monitor jack to check the output value. For example, in
order to output 12mA with output 4 – 20mA DC, adjust the
setpoint so that the monitor output becomes 5V.
• Setpoint adjustment
Adjust the setpoint while checking the monitor output.
MS
Base Socket
Monitor
+
Setpoint Adj.
Front Cover (open)
EM-1651 Rev.8 P. 1 / 2

Advertisement

loading
Need help?

Need help?

Do you have a question about the MS and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for MG MS

  • Page 1 10 minutes is required for Adjust the setpoint while checking the monitor output. satisfying complete performance described in the data sheet. EM-1651 Rev.8 P. 1 / 2 MG CO., LTD. www.mgco.jp 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
  • Page 2 LIGHTNING SURGE PROTECTION We offer a series of lightning surge protector for protec- tion against induced lightning surges. Please contact us to choose appropriate models. EM-1651 Rev.8 P. 2 / 2 MG CO., LTD. www.mgco.jp 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...