Economizer Module Wiring Details; S-Bus Sensor Wiring - Carrier RHV090-120 Installation Instructions Manual

Single package rooftop heat pump with r-410a refrigerant and x-vane fan technology
Table of Contents

Advertisement

Storage Temperature:
–40°F to 150°F (–40°C to 65°C)
Shipping Temperature:
–40°F to 150°F (–40°C to 65°C)
Relative Humidity:
5% to 95% RH non-condensing

ECONOMIZER MODULE WIRING DETAILS

Use Fig. 42 and Tables 6 and 7 to locate the wiring
terminals for the Economizer module.
NOTE: The four terminal blocks are removable. You can
slide out each terminal block, wire it, and then slide it back
into place.
MAT
MA
MAT
MA
OAT
OA
OAT
OA
S-BUS
SB
SB
S-BUS
SB
SB
SB
SB
V
IAQ 2-10
C
R
IAQCOM
IAQ 24V
V
C
ACT 2-10
R
NA
ACT COM
ACT 24V
50040839-001
Rev. G
Fig. 42 — W7220 Wiring Terminals
RHV-090-120-01SI
NA
AUX2-
NA
A2
OCC
OCC
E-GND
EXH1
EX
A1
AUX1-O
Certified FDD Product
California Title 24, Part 6
HJW10
www.energy.ca.gov
Y2-
Y2I
Y2O
Y2-O
Y1I
Y1-
Y1O
Y1-O
C
R
C
R
50048848-002
Rev. A
Specifications subject to change without notice.
Table 6 — Economizer Module — Left Hand
Terminal Blocks
LABEL
TYPE
Top Left Terminal Block
MAT
20k NTC
Mixed Air Temperature Sensor (Polarity
MAT
and COM
Insensitive Connection)
OAT
20k NTC
Outdoor Air Temperature Sensor (Polarity
OAT
and COM
Insensitive Connection)
S-BUS
S-BUS
Enthalpy Control Sensor
S-BUS
(Sylk
a
Bus)
(Polarity Insensitive Connection)
Bottom Left Terminal Block
Air Quality Sensor Input (e.g. CO
IAQ 2-10
2-10 vdc
sensor)
IAQ COM
COM
Air Quality Sensor Common
IAQ 24V
24 vac
Air Quality Sensor 24 vac Source
ACT 2-10
2-10 vdc
Damper Actuator Output (2-10 vdc)
ACT COM
COM
Damper Actuator Output Common
ACT 24-v
24 vac
Damper Actuator 24 vac Source
NOTE(S):
a Sylk is a trademark of Honeywell International Inc.
Table 7 — Economizer Module — Right Hand
Terminal Blocks
LABEL
TYPE
Top Right Terminal Blocks
AUX2 I
24 vac IN
The first terminal is not used.
Shut Down (SD) or HEAT (W)
Conventional only
OCC
24 vac IN
and
Heat Pump Changeover (O-B) in Heat
Pump mode.
E-GND
E-GND
Occupied/Unoccupied Input
EXH1
24 vac OUT Exhaust Fan 1 Output
Programmable:
Exhaust fan 2 output
or
AUX1 O
24 vac OUT
ERV
or
System alarm output
Bottom Right Terminal Blocks
Y2 in - Cooling Stage 2 Input from space
Y2-I
24 vac IN
thermostat
24 vac OUT Y2 out - Cooling Stage 2 Output to stage
Y2-O
2 mechanical cooling
Y1 in - Cooling Stage 2 Input from space
Y1-I
24 vac IN
thermostat
Y1 out - Cooling Stage 2 Output to stage
Y1-O
24 vac OUT
2 mechanical cooling
C
COM
24 vac Common
R
24 vac
24 vac Power (hot)

S-BUS SENSOR WIRING

The labels on the sensors and controller are color coded for
ease of installation. Orange labeled sensors can only be
wired to orange terminals on the controller. Brown labeled
sensors can only be wired to S-bus (brown) terminals. Use
Fig. 43 and Table 6 to locate the wiring terminals for each
S-Bus sensor.
Use Fig. 43 and Table 8 to locate the wiring terminals for
each enthalpy control sensor.
DESCRIPTION
2
DESCRIPTION
29

Advertisement

Table of Contents
loading

Table of Contents