Appendix 1 Specifications - BPE PS50 Series User Manual

Modular ups
Table of Contents

Advertisement

Model
Cabinet capacity (VA/W)
Module capacity (VA/W)
Max. module number
Phase
Rated Voltage
Voltage Range
Input
Frequency Range
Power Factor
Current THDi
Bypass Voltage
Range
Phase
Rated Voltage
Power Factor
Voltage Regulation
Frequency
Crest Factor
Output
THD
Overload
Battery
Voltage

Appendix 1 Specifications

100kVA
50k~100k
50k~100k
2+1
138~485Vac
◆ At 40°C: The UPS works at full load when the voltage is
323–485Vac and is derated load when the
voltage is 323–138Vac
◆ At 30°C: The UPS works at full load when the voltage is
305–485Vac and is derated load when the
voltage is 305–138Vac
Max.voltage: 220V:+25 %( optional +10%, +15%, +20%);
Min. voltage:-45 %( optional -10%, -20%,-30%)
Frequency protection range: ±10%
Utility
±1%/±2%/±4%/±5%/±10%of the rated frequency(optional)
Mode
Battery
Mode
Inverter overload capability:
◆ 105% < load ≤ 110%: transfer to bypass mode after 60
min
◆ 110% < load ≤ 125%: transfer to bypass mode after 10
min
◆ 125% < load ≤ 150%: transfer to bypass mode after 1
min
Bypass overload capability:
◆ Temperature ≤ 30°C, load ≤ 135%: run for a long time
◆ Temperature ≤ 40°C, load ≤ 125%: run for a long time
◆ 1000% load: run for 100 ms
Optional Voltage:
±180V/192V/±204V/±216V/±228V/±240/±252/±264/±276/±
288/±300Vdc(30/32/34/36/38/40/42/44/46/48/50pcs
optional)
360Vdc~600Vdc (30~50 pcs, 30 pcs define, 36~50 pcs no
power derating; 32~34 pcs output power factor 0.9;30 pcs
output power factor 0.8;)
74
150kVA
200kVA
50k~150k
50k~200k
50k~150k
50k~200k
50k / 50k
3
4
3 Phase 4 Wires and Ground
380/400/415Vac
40Hz-70Hz
≥0.99
≤3%(100% nonlinear load)
230V:+20 %( optional +10%, +15%);
240V:+15 %( optional +10%);
3 Phase 4 Wires and Ground
380/400/415Vac
1
±1%
(50/60±0.1)Hz
3:1
≤2% with linear load
≤4% with non linear load
250kVA
50k~250k
50k~250k
5