LG LD097HV4 Engineering Manual page 79

Single-zone ceiling-concealed ducted system
Table of Contents

Advertisement

Outdoor Unit (36,000 Btu/h Capacity) Service Access and Allowable Clearances
When installing the outdoor unit, consider service, inlet, and outlet, and minimum allowable space requirements as illustrated in the following
diagrams.
Minimum 11-13/16
Minimum 11-13/16
Ensure that the space at the back of the outdoor unit is a minimum of 11-13/16 inches, and
include a minimum of 23-5/8 inches at the right side of the unit for service.
Clearance Requirements when Different Obstacles are Present (Unit: Inch).
Obstacle on the suction side only.
Obstacles above and on the air intake side. Obstacles above, on the air intake side,
Minimum 11-13/16
F e n
F e n
c e o
c e o
o b s
o b s
r
r
t a c l
t a c l
e s
e s
Obstacles on the suction side and
on both left and right sides.
and on both left and right sides
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Minimum 11-13/16
Air inlet grille
Air inlet grille
Minimum 23-5/8
If the outdoor unit discharge side faces a wall, include a minimum of 19-11/16 inches
between the outdoor unit and the wall. Install the outdoor unit so that the discharge port is
set at a right angle to the wind direction.
CLEARANCES
Outdoor Unit
Strong
Strong
wind
wind
Blown
Blown
air
air
Minimum 19-1/16
Unit: Inch
DUCTED | 79
Strong
Strong
wind
wind

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ld127hv4Lh248hv4Lh368hv4Ld187hv4

Table of Contents