LG LD097HV4 Engineering Manual page 50

Single-zone ceiling-concealed ducted system
Table of Contents

Advertisement

ACCESSORIES
LG Monitoring View (LGMV) Diagnostic Software and Cable
LGMV software allows the service technician or commissioning agent to connect a computer USB
port to the outdoor unit main printed circuit board (PCB) using an accessory cable without the need
for a separate interface device. The main screen for LGMV allows the user to view the following real
time data on one screen:
• Actual inverter compressor speed
• Target inverter compressor speed
• Actual outdoor fan speed
• Target outdoor unit fan speed
• Actual superheat
• Target superheat
• Actual subcooler circuit superheat
• Target subcooler circuit superheat
• Main EEV position
• Subcooling EEV position
• Inverter compressor current transducer
value
• Outdoor air temperature
• Actual high pressure/saturation temperature
• Actual low pressure/saturation temperature
• Suction temperature
• Inverter compressor discharge temperature
• Constant speed compressor discharge
temperature
Additional screens can be accessed by tabs on the main screen:
1. Cycleview: Graphic of internal components including:
• Compressors showing actual speeds
• EEVs
• Indoor Units
• Liquid injection valves
2. Graph:
Full screen graph of actual high and low pressures and high and low pressure limits. A
sliding bar enables user to go back in time and view data.
3. Control IDU: Enables user to turn on all IDU's default setpoints of 86°F in heat mode or 64°F in
cool mode.
4. Setting: Converts metric values to imperial values.
5. Making Data: Recording of real time data to a separate file created to be stored on the user's computer.
6. Loading Data: Recorded data from a saved ".CSV" file can be loaded to create an LGMV session.
7. Electrical Data: The lower half of main screen is changed to show the following:
• Inverter compressor
- Amps
- Volts
- Power Hz
- Inverter control board fan Hz
In lieu of connecting to the outdoor unit, user has the option to connect to the indoor unit with the use of a USB to RS-485 connector kit.
When connected through the indoor unit, user will not be able to record data.
This software can be used to both commission new systems and troubleshoot existing systems. LGMV data can be recorded to a ".CSV" file
and emailed to an LG representative to assist with diagnostic evaluations.
Recommended Minimum PC Configuration:
• CPU: Pentium
IV 1.6 GHz
®
• Operating System: Windows
• Main Memory: 256 MB
LGMV is available in different formats, including Mobile LGMV, which is a app for use on wireless devices. Contact your LG
Sales Representative for more information.
50 | DUCTED
• Front outdoor coil pipe temperature
• Back outdoor coil pipe temperature
• Liquid line pipe temperature
• Subcooler inlet temperature
• Subcooler outlet temperature
• Average indoor unit (IDU) pipe temperature
• Inverter compressor operation indicator
light
• Four-way reversing valve operation
indicator light
• Pressure graph showing actual low pres-
sure and actual high pressure levels
• Error code display
• Operating mode indicator
• Target high pressure
• Target low pressure
• PCB (printed circuit board) version
• Software version
• Installer name
• Temperature and pressure sensors
• Four-way reversing valve
• Outdoor fans showing status and speeds
• Constant compressor
- Current transducer value
- Phase
NT/2000/XP/Vista
®
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
• Model no. of outdoor units
• Site name
• Total number of connected indoor units
• Communication indicator lights
• Indoor unit capacity
• Indoor unit operating mode
• Indoor unit fan speed
• Indoor unit EEV position
• Indoor unit room temperature
• Indoor unit inlet pipe temperature
• Indoor unit outlet pipe temperature
• Indoor unit error code
• Hard Disk: 600 MB when operating
• Web Browser: Internet Explorer
Figure 42: Sample Cycleview.