Setup - - Thermostat
Auto Mode Setup:
S Enable/Disable Auto Changeover mode (default = Enable).
S Auto Changeover Time may be adjusted 5 to 120 minutes,
(default = 30 minutes).
When Auto mode is enabled (factory default) a change from heat
to cool (or vice versa) will not occur until an opposite mode
demand has existed for 30 minutes. If the setpoint is changed, the
30 minute timer is deleted.
Heat/Cool Deadband:
S 0 to 6_F (0 to 3_C), (default = 2_F).
The minimum difference enforced between heating and cooling
desired temperatures. This can allow one setting to "push" the
other to maintain this difference.
Offsets:
This option allows calibration (or deliberate miscalibration) of the
temperature and humidity sensors. These offsets are added to the
actual temperature/humidity values (default = 0).
S Zone 1 Offset: - -5 to +5_F (- -3_C to +3_C).
S Outside Temp Offset: - -5 to +5_F (- -3_C to +3_C).
S Humidity Offset: - -10 to +10%.
Elevation:
0 to 10000 feet. This value is used to correct the static pressure
readings the system performs.
Cycles Per Hour:
S Maximum cycles per hour = 4 (default) or 6.
Programming:
S ON (default)- - allows program schedule to be set by user.
S OFF - - system becomes non- -programmable
S Periods Per Day = 2 or 4 (default = 4)
S Programmable Fan On/Off (default = Off). If ON is selected, fan
can be set to Auto, Low, Med, or High.
Smart Recovery:
S On or Off (default = On)
Applies to programmable operation only. Will start recovery 90
minutes prior to schedule change in both heating and cooling
mode. Refer to operational information for more detail.
English/Metric Display:
S _F or _C (default = _F)
Reset Factory Defaults:
Program Schedule:
S Yes/No to reset back to Energy Star default Time and Temp
schedules.
User Settings:
S Yes/No to reset the user settings in the Advanced Setup to
factory default settings.
Install Settings:
S Yes/No to reset install settings in Install/Service menus to factory
default settings.
Last 10 System Events:
S Yes/No to reset last 10 system events under Service Info menu.
Setup - - Furnace
Upon a first time start- -up of the Evolution Zone Control, the
furnace DIP switch settings will be copied to the furnace setup
menu. Any changes can then be made from the Evolution Zone
Control.
Furnace Airflow:
S COMFORT (default)
S EFFICIENCY
Selects the airflow of the furnace when heating. EFFICIENCY is
the airflow used to meet specified ratings, COMFORT is a
decreased airflow used to increase the output air temperature and
provide increased comfort.
Cooling Airflow:
S COMFORT (default) - - cooling airflow is varied depending on
humidity and temperature demands settings. This selection
enables the full dehumidify and comfort capabilities of the
system. When COMFORT is not selected, the unit will not run
reduced airflows for dehumidification.
S EFF 325 - - fixed airflow used to achieve specified ratings - - no
dehumidification airflow reduction. This is nominally 325
CFM/ton, but will vary if a 2- -stage outdoor unit is used.
S EFF 350 - - fixed airflow used to achieve specified ratings - - no
dehumidification airflow reduction. This is nominally 350
CFM/ton, but will vary if a 2- -stage outdoor unit is used.
S MAXIMUM - - 400 CFM/ton.
S QUIET- - minimum cooling airflow that the system can safely
run (typically 300 CFM/ton). Use this setting if duct noise is a
severe problem. Note that duct sweating in high humidity
environments could be an issue.
Heat Pump Heating:
S COMFORT (default) Heat Pump airflow is varied depending on
outdoor temperature to maximize comfort.
S EFF 325 - - fixed airflow used to achieve specified ratings - - no
dehumidification airflow reduction. This is nominally 325
CFM/ton, but will vary if a 2- -stage outdoor unit is used.
S EFF 350 - - fixed airflow used to achieve specified ratings - - no
dehumidification airflow reduction. This is nominally 350
CFM/ton, but will vary if a 2- -stage outdoor unit is used.
S MAXIMUM - - 400 CFM/ton.
Dehum Airflow:
S NORMAL (factory default) - - When equipment is running to
dehumidify, the airflow is allowed to adjust to a minimum to
satisfy the dehumidification call.
S HIGH - - Minimum airflow during the dehumidify mode is
increased to reduce duct and register sweating. Also increases
minimum airflow during normal cooling operation to reduce
duct sweating.
Low Heat Rise
S ON
S OFF (default)
Set to ON if the system contains a bypass humidifier. The ON
setting will increase the furnace low heat airflow.
Staging
S SYSTEM (default)
S LOW
S LOW- -MED
S LOW- -HIGH
S MED
S MED- -HIGH
S HIGH
NOTE: Two- -stage furnace has LOW and HIGH selections only.