Standard coverage, standard response concealed pendent sprinkler, k-factor 5.6 (80 metric)

Advertisement

Model SY8051
Standard Coverage, Standard Response Concealed Pendent
Sprinkler, K-factor 5.6 (80 metric)
Use Sentry Sprinklers recommended wrench to install the sprinkler. Slide the sprinkler wrench around
the sprinkler frame arms and press the wrench down to engage sprinkler wrench flats. Rotate the
wrench clockwise to tighten the sprinkler head. The frame arms must be parallel to the pipe. Never
tighten the sprinkler from sprinkler arms. Any torque applied to the frame arms will dislodge the bulb
seating assembly causing the sprinkler to leak.
The concealed sprinkler must not be used in any application where the air pressure above the ceiling
is greater than that below it. Downdraft through the Mounting Cup could delay sprinkler operation in a
fire condition.
Only use Sentry Sprinklers recommended wrench to install the sprinkler.
Exercise caution when installing the sprinkler. If the sprinkler is damaged during installation, do not
attempt to fix it, replace it immediately.
After the ceiling has been completed with a 2 ½" (64mm) to 2
13/16" (72mm) diameter clearance hole, remove and discard
the protective cap and verify that the sprinkler is intact.
Do not attempt to make up for insufficient adjustment in
the sprinkler assembly by under or overtightening the
sprinkler Mounting Cup Assembly. Instead, readjust the
position of the sprinkler fitting.
Do not remove Sprinkler Protective Cap until you are
ready to install the Cover Plate Assembly.
Absence of the Cover Plate Assembly may delay the sprinkler
operation time in a fire situation.
For additional details, refer to NFPA and UL for installation
guidelines.
Care and Maintenance:
The owner is responsible for maintaining their fire protection system
and devices in proper operating condition. Refer to NFPA 25 for
inspection, testing and maintenance requirements. It is recommended
that an automatic sprinkler system be inspected quarterly by qualified
inspection personnel.
Sprinklers must never be shipped and or stored where ambient
temperature exceeds 100° F / 38° C. Inspect Sprinkler before and
after installation. Exercise caution during installation to avoid damage
to the sprinkler. Damaged sprinkler due to dropping, striking, and or
wrench slippage must be replaced.
Cover Plate Assembly
10967 Lake Underhill Rd, Unit 103 Orlando, Florida 32825 Tel:+1-407-482-9282 Fax:+1-407-482-9476
www.SentrySprinklers.com
Page 3/4