Download Print this page

Sentry SY8051 Manual page 2

Standard coverage, standard response concealed pendent sprinkler, k-factor 5.6 (80 metric)

Advertisement

Approval Material Standard
UL
1- Frame:
2- Mounting Cup
3- Button Seal:
4- Spring Seal:
5- Bulb:
6- Enclosure
Coverage:
For coverage area and placement of the sprinkler refer to NFPA 13
standard.
Guarantee:
Sentry Sprinklers shall replace any of its products if found to be defective
in materials or workmanship for a period of one year from order date.
The guarantee does not cover wear and tear or improper installation.
Installation:
All sprinkler heads must be inspected prior to installation. If a sprinkler is damaged, the bulb is cracked,
the bulb has loss of liquid and or lost its protective cap, do not install the sprinkler and contact Sentry
Sprinklers for replacement. With the sprinkler held in the horizontal orientation, a small air bubble
should be present inside the glass bulb.
10967 Lake Underhill Rd, Unit 103 Orlando, Florida 32825 Tel:+1-407-482-9282 Fax:+1-407-482-9476
Standard Coverage, Standard Response Concealed Pendent
Sprinkler, K-factor 5.6 (80 metric)
Brass
Teflon Tape
Stainless Steel
Glass Bulb with Glycerine Solution,
5mm Nominal
www.SentrySprinklers.com
Model SY8051
7- Set Screw:
8- Deflector:
9- Cover Plate
10- Ejection Spring
11- Label
Sprinkler Mounting Cup Assembly
Brass
Bronze
Page 2/4