36” open corner non-circulating (smooth face) wood burning fireplace
Table of Contents

Advertisement

Figure 12
INSTRUCTIONS WHEN OFFSET OF CHIMNEY IS
NEEDED
Installing offset and return elbow (30E-8DM)
1. To achieve desired offset, you may install
combination of 12", 18", 24", 36" and 48" length of
double wall pipe (see figures 12 and 13).
2. The chimney weight above the offset rest on return
elbow. Straps must be securely fastened to rafters or
joists (see figure 14, details A & B).
3. Maximum length of pipe between supports (return
elbow or chimney support V12S-8DM) is 6' of
angled run. Maximum of two (2) 6' angled run
sections per chimney system.
OFFSET
A
4 - 3/8
9 - 3/4
12 - 3/4
15
18
21 - 1/4
23 - 3/4
27 - 3/4
30
33
36
38 - 1/4
41 - 1/4
45
46 - 3/4
51
53 - 1/4
56 - 1/4
106 - 1/4
59 - 1/4
111 - 1/2
61 - 3/4
115 - 1/2
64 - 3/4
120 - 3/4
68 - 1/4
70
74 - 1/4
137 - 1/2
76 - 3/4
141 - 1/2
79 - 3/4
146 - 3/4
Figure 13
OFFSET CHART
TYPICAL OFFSET INSTALLATIONS
All pipe connections between
the offset and return must be
secured with two screws,
only on the outer pipe, and
must not penetrate the inner
stainless.
RISE
CHIMNEY LENGTH
B
48"
36"
24"
18"
16 -3/8
ELBOW SET ONLY
25 - 1/2
30 - 3/4
1
34 - 3/4
1
40
1
46 - 1/4
1
49 - 1/4
1
1
56 - 3/4
1
60 - 3/4
1
1
66
1
71
1
1
75
2
80 - 1/4
1
1
86 - 3/4
2
89 - 1/2
1
1
97
1
1
101
2
1
2
1
1
1
2
2
1
127
1
2
130
2
1
1
2
1
2
1
4
Figure 14
FIRESTOP SPACERS: (FS-8DM)
Firestop spacers are required at each point where the chimney
penetrates a floor or ceiling joist space. Their purpose is to
12"
establish and maintain the required clearance between the
1
chimney and the combustible materials.
1
They also provide complete separation from one floor space to
1
another floor or attic space as required by most codes. When
the double wall pipe passes through a framed opening into an
1
attic space, the firestop must be place into the attic floor as in
1
figure 15.
1
When the pipe passes through a framed opening into a living
1
space above, the firestop must be placed onto the ceiling from
1
below as shown in figure 15.